2
19
2. Principle of Operation
The main function of the control unit is to keep temperature in the water jacket at the preset
value. The task is realized by measuring temperature (T3) and controlling the cold air choke valve
(PP) properly. Fireplace operation temperature is defined by the
parameter (see PARAMETERS LEVEL 1).
If the fireplace temperature (T3) is higher than the
parameter the
choke valve is gradually shut off limiting air supply, and if the temperature (T3) is lower than the
parameter the choke valve is gradually opened up.
The second function is control the loading pump of the BUF container (P2). The pump P2 runs if the
fireplace temperature exceeds “
”
and is above the buffer temperature (T1) by the
parameter (see see PARAMETERS LEVEL 1).
The third function is to control the WAW pump loading the warm applicable water accumulator
(WAW). The pump P1 operates if temperature of heat source (BUFFER for standard configuration,
FIREPLACE for a configuration with the buffer type COMBO see fig.1) exceeds the
value and is higher than the WAW accumulator temperature (T2) by the
parameter (see
PARAMETERS LEVEL 1).
The next function is to control the circulating pump (P3) of central heating system. The pump
works if the buffer temperature exceeds the
value. It
’
s possible to activate the WAW priority
function - - see the description of operation modes of the CH pump.
The control unit is also equipped with the clock to control the WAW priority in selected times
of day.
<20>
“
FIREPLACE Temp.
”
<20>
“
FIREPLACE Temp.
”
<20>
“
FIREPLACE Temp.
”
BUFF ON
<61>
DeltaBUF
WAW ON
DeltaWAW
CH ON
!
The fireplace can also be equipped with warm air distribution system based on the RT-03C control
unit. The RT-03C control unit measures temperature in the chamber of the fireplace air ventilator and
controls its rotation speed in manual or automatic mode.
Fig. 1a Basic operation configuration of the control unit
Admission
date
Realization
date
Signature
Remarks
WAW
CH
FIREPLACE