background image

7

14

3.1 Time zones

The control unit is equipped with the clock, which enables the automatic change of the control

unit operation at different times of day. 24 hrs are divided into 5 time zones (

) . Each

zone has a start time FROM and an end time TO. The same start and end time means the zone isn

t

active, which doesn

t change the settings of the control unit. The time zones can overlap each other in

that case binding are the settings for the active zone of higher number.

In the control unit there

s a defualt zones program as follows:

$1, $2, $3, e4, e5

ZONE $1

FROM 6.00 TO 8.00

ZONE $2

FROM 14.00 TO 17.30

ZONE $3

FROM 20.00 TO 22.30

ZONE e4

FROM 23.00 TO 5.30

ZONE e5

FROM 8.00 TO 13.30

The zones $1...$3 relates to the pump priority-loading the WAW container in the mode

and

(see p.2.4)

The zones e4...e5 enable lowering the preset temperature of the fireplace by the
parameter at the limited demand for the heat. If the <25>

parameter is set to OFF

then at the active ECO zones the loading of the WAW container will be turned off.
! At the default settings the time zones are not active. In order to activate them you need to set the
<14>

parameter to ON.

CLOCK

Special

<22> ECO Temp.

WAW in ECO zone

Time zones

3.2 Screens

Alarm screens

ALARM

BUF temp. sensor (T1) damaged

WAW temp. sensor (T2) damaged

Fplace temp. sensor (T3) damaged

too high temp. of the fireplace

too high temp. of the buffer

is not seen till the following alarm situation takes place:

1. Damage of the T1(BUFFER) sensor. The

text shows up.

2. Damage of the T2(WAW) sensor . The

text shows up.

The alarm dosen

t initialize if the sensor is not mounted.

3. Damage of the T3 sensor of the fireplace. The

text shows

up.

4. The exceeding of

The

text shows up.

5. The exceeding of

The

text shows up.

the limit temperature of the fireplace defined by the

parameter.

the limit temperature of the buffer defined by the

parameter.

<21> ALARM Temp.

<24> BUF ALARM

Temp.

Alarm

text

Alarm situation is accompanied by a broken sound alarm that can be turned off by pressing the
CONFIRM button (6)

In the emergency of exceeding the temperature of the fireplace the CH/BUF pump

turns on to cool off the fireplace.

!

P

ARAMETERS LEVEL 4

OFF/ON

OFF

Setting the value of

ON

causes the recall of all parameters to

their default pre-sets and restarts the control unit

RESET

FUNCTION

NAME

RANGE

DEFAULT

90

91

No

ProdNo.

0.....n

1

Number of the parameters set - dependent on fireplace producer

93

BUFFER
COMBO

99

Service
Screen

OFF/

ON

OFF

The ON value causes diagnostics screen to be added
for servicing.

Password

The changes of important parameters are possible only at unlocked password. To unlock the password you
need to input proper sequence of digits with the buttons

+/-

. With the CHOOSE button (7) to change the

digits position and CONFIRM button (6) to acknowledge all and finish the procedure of changing the
password. The unlocked password is set to

0000

. Once again entering into the password change procedure

causes a new password to be set.

!

!

PASSWORD

9999

HAS CONSIDERABLE MEANING. IT CAUSES THE REACTIVATION OF THE PREVIOUS

PASSWORD IF PRESENT WITHOUT IT BEING EXPOSED.

PASSWORD OF PRODUCER'S SERVICE IS UNIQUE AND IS NOT DEPENDENT ON THE USER'S PASSWORD-

IT SHOUDN'T BE EXPOSED TO THE USER. INSTEAD OF THAT THE SERVICE CAN SET THE USER HIS OWN
PASSWORD.

Examples of passwords:

1.The control unit is installed with the unlocked password. The user can enter his own password e.g.

1234

.

From this moment the important parameters cannot be altered without the password being unlocked (that is,
resetting the password

1234

). After changing essential parameters the user can leave the control unit

unlocked, set any new password or enter

9999

, which activates the password

1234

2. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman enter the secret password or

9999

, the user still hasn't access to the important parameters.

3. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman leaves the control unit
unlocked, the user now has access to the important parameters. He can enter his own password like in example
No. 1.

4. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman sets the password e.g.

1234

and tells it to the user, the user has access to the important parameters but without knowing the password

the other persons cannot make the changes.

5. The user has the unlocked control unit or his own password. Serviceman decides, the user though oughtn't
have access to the important parameters. The serviceman locks the control unit with his secret password, which
removes the user's password and locks the control unit.

6. Serviceman doesn't have to know the user's password. Always he can use his own secret password and at

the end lock with the

9999

, which reactivates the user's password.

92

PASSWORD

0

9999

0000

0000

PASSWORD OFF

----

PASSWORD ON

OFF/

ON

OFF

OFF- standard operation configuration (see fig.1a)
ON- operation with BUFFER COMBO (WAW inside buffer)

Summary of Contents for RT-08G-BUF

Page 1: ...ion conditions 0 50 C humidity 10 90 Housing protection class Fuse 6 3A 250V Number of outputs to control pumps Number of nonvoltage outputs 1 Number of outputs to control the choke valve drive Number...

Page 2: ...temperature of heat source BUFFER for standard configuration FIREPLACE for a configuration with the buffer type COMBO see fig 1 exceeds the value and is higher than the WAW accumulator temperature T2...

Page 3: ...d ISO9001 2000 CERTIFICATE No 133 2004 of 01 2004 Polish Foreign Trade Chamber The last two digits of the year in which the CE marking was affixed 07 Fig 1b Alternative operation diagram of the buffer...

Page 4: ...HE CONTROL UNIT MADE BY A USER CAN BE THE CAUSE OF SAFETY CONDITIONS DETERIORATION AND CAN EXPOSE THE USER TO ELECTRIC SHOCK OR DAMAGE DEVICES SUPPLIED Date of sale Seller s signature and stamp Zak ad...

Page 5: ...is equipped with the CONTROL relay whose contacts can be used e g to switch off another heat source when the fireplace works The parameter definesthefunctionof therelaymoreprecisely see PARAMETERS LEV...

Page 6: ...nged parameter not confirmed for 10 secs is not acceptedby thecontrolunit ON OFF CHOOSE CONFIRM Fig 2 Control panel view 1 Control unit status diode alarm red standby orange operation green manual MAN...

Page 7: ...only at unlocked password To unlock the password you need to input proper sequence of digits with the buttons With the CHOOSE button 7 to change the digits position and CONFIRM button 6 to acknowledge...

Page 8: ...urning off the pumps It prevents from often switchovers especially if there s another heat source in the heating system Buffer limit temperature at which the alarm generates 75 95 o C 85 o C Fireplace...

Page 9: ...he exceeding turns off the loading pump 42 Minimum temp of WAW 30 99 o C 50 o C Minimal temperature of WAW container The exceeding turns on the loading pump 43 Loading temp of WAW special 30 99 o C 65...

Page 10: ...uttons or Pressing theCONFIRM button 6 confirmsthechanges theclockfieldwillstopblinking Normallythe equalsto 0 namelytheparametersaren tavailable After changing the level to 1 2 3 or 4 successive scre...

Reviews: