background image

8

13

Screen of the fireplace operation

shows the current temperature of the fireplace and the level of

choke valve opening.

Temperature of

the water jacket

of the fireplace (T3)

Current

time

Time

zone

Operation mode

of

the fireplace

Preset

temperature

Choke valve

opening

It

s a stable state, that is, in order to change it you need to press the CHOOSE button (7)

During appearing this screen you can change the preset temperature of the fireplace (the

parameter). After pressing the CONFIRM button (6) the preset temperature

blinks whose value can be altered with the buttons

+

(4) or

-

(5) To confirm the changes you need

to press the CONFIRM button (6) once more.

<20>

FIREPLACE Temp.

!

!

At the economic time zones

e4

or

e5

the displayed temperature is corrected by the drop

(the

parameter) that is indicated by the

-

minus sign instead of C..

During the loading of the WAW accumulator in the

mode the preset

temperature gets automatically raised up to the

parameter

value that is indicated by the

+

plus sign

If the manual mode is set (

) (the green LED diode (7) blinks.) you

can manually control the choke valve-. The

+

button (4) causes the opening of the choke valve

(one step

10%) and the

+

button (5) causes its closing.

<22> ECO Temp.

WAW MODE=SPECIAL

<43> Loading temp. of WAW special

FIREPLACE MODE=MAN

o

FIREPLACE

50

ChokeV
State OFF

0...100%

0%

Position of the choke valve in the

state

turned off (0%-full shut-off, 100% - full opening)

power supply

32

Stoptime

of CH PUMP

0...10mins

0min

4mins

45

24

21

PARAMETERS LEVEL 3

PARAMETERS CAN BE CHANGED AT THE UNLOCKED PASSWORD

No

NAME

RANGE

DEFAULT

SETTING

FUNCTION

Break time of the CH pump in the cyclical mode. After
that time the pump turns on for 45secs.

33

Hysteresis
of PUMPS

1...10

o

C

1

o

C

Temperature hysteresis of turning on/off the pumps.
The temperature difference between turning on
and turning off the pumps. It prevents from often
switchovers, especially if there's another heat source
in the heating system.

Buffer limit temperature at which the alarm generates.

75...95

o

C

85

o

C

Fireplace temperature at which the alarm turns on.

5...25

o

C

10

o

C

Decreasing fireplace temperature in relation to preset temperature
at whose exceeding the countdown of 30mins begins up to the
switch-off of fireplace (stop condition at

)

FIREPLACE MODE=AUTO

BUF ALARM

Temp.

ALARM
Temp.

FPLACE OFF

Temp.

Rundown time of the

pump . The extending of the time

for the pump operation after finishing loading the WAW container
.

WAW

Rundown

Time of

WAW PUMP

1...30mins

23

0...6

2

Switch-on of the

relay if

CONTROL

2

WAW temperature is higher than

ControlRelayTemp

3
4
5
6

BUF pump (P2) runs

CONTROL
Relay

1...2

1

1

2

ChokeV
Mode

Control type of the choke valve

Dynamic control - servomotor of the choke valve is active
only if the position change of the valve is needed.

Continuous control - servomotor of the choke valve is always
active.

12

51

!

Parameter number (No.) is of auxiliary role - it helps to identify the name e.g. for different

language versions

61

62

63

DeltaBUF

-10...+10

o

C

1

o

C

Minimal temperature difference between fireplace and buffer
required for the BUF pump (P2) to run. Negative values have
application for big buffers

OFF - the pump loading the buffer runs normally
ON- the pump loading the buffer runs cyclically at
the WAW priority loading(only in case of BUFFER COMBO,
that is, at the <93> = ON parameter setting

WAW/BUF

Priority

-

OFF/ON

OFF

Rundown
Time

-

BUF

0..30mins

1min

Rundown time of the BUF pump. Extending the run time of
the pump after ending the loading of the BUF

75...95

o

C

85

o

C

0

1

fireplace temp. higher than

ControlRelayTemp

Buffer temp. higher than

ControlRelayTemp

WAW pump (P1) runs
CH pump (P3) runs
ALARM is turned on (see

Alarm screens

)

16

Control-
RelayTemp

5...95

o

C

60

o

C

Limit temperature at which the CONTROL relay turns on.
(Depending on the <12> CONTROL Relay parameter.)

Summary of Contents for RT-08G-BUF

Page 1: ...ion conditions 0 50 C humidity 10 90 Housing protection class Fuse 6 3A 250V Number of outputs to control pumps Number of nonvoltage outputs 1 Number of outputs to control the choke valve drive Number...

Page 2: ...temperature of heat source BUFFER for standard configuration FIREPLACE for a configuration with the buffer type COMBO see fig 1 exceeds the value and is higher than the WAW accumulator temperature T2...

Page 3: ...d ISO9001 2000 CERTIFICATE No 133 2004 of 01 2004 Polish Foreign Trade Chamber The last two digits of the year in which the CE marking was affixed 07 Fig 1b Alternative operation diagram of the buffer...

Page 4: ...HE CONTROL UNIT MADE BY A USER CAN BE THE CAUSE OF SAFETY CONDITIONS DETERIORATION AND CAN EXPOSE THE USER TO ELECTRIC SHOCK OR DAMAGE DEVICES SUPPLIED Date of sale Seller s signature and stamp Zak ad...

Page 5: ...is equipped with the CONTROL relay whose contacts can be used e g to switch off another heat source when the fireplace works The parameter definesthefunctionof therelaymoreprecisely see PARAMETERS LEV...

Page 6: ...nged parameter not confirmed for 10 secs is not acceptedby thecontrolunit ON OFF CHOOSE CONFIRM Fig 2 Control panel view 1 Control unit status diode alarm red standby orange operation green manual MAN...

Page 7: ...only at unlocked password To unlock the password you need to input proper sequence of digits with the buttons With the CHOOSE button 7 to change the digits position and CONFIRM button 6 to acknowledge...

Page 8: ...urning off the pumps It prevents from often switchovers especially if there s another heat source in the heating system Buffer limit temperature at which the alarm generates 75 95 o C 85 o C Fireplace...

Page 9: ...he exceeding turns off the loading pump 42 Minimum temp of WAW 30 99 o C 50 o C Minimal temperature of WAW container The exceeding turns on the loading pump 43 Loading temp of WAW special 30 99 o C 65...

Page 10: ...uttons or Pressing theCONFIRM button 6 confirmsthechanges theclockfieldwillstopblinking Normallythe equalsto 0 namelytheparametersaren tavailable After changing the level to 1 2 3 or 4 successive scre...

Reviews: