IX. 

System Faults 

1. 

Fault Condition:

 

a. 

Audible Indicator 

– 

When any fault occurs, a steady tone will be emitted from the 

Command Unit. 

b. 

Visual Indicator for Opens 

– 

When an open occurs on an AOR-CSE Station cable run, 

the respective 

FAULT 

LED(s) will flash on the Command Unit panel indicating the 

specific station location(s) with the fault. 

c. 

Visual Indicator for Shorts 

– 

When a short occurs on an AOR-CSE Station cable run, 

the respective 

FAULT 

LED(s) will flash on the Command Unit panel indicating the 

specific station location(s) with the fault. 

d. 

Visual Indicator for PSTN/POTS Telephone Line Fault 

– 

When the PSTN/POTS 

telephone line has an open or a short, the 

OUTSIDE LINE FAULT 

LED will flash on the 

Command Unit panel. 

e. 

Visual Indicator for System Ground Fault 

– 

When a system ground fault occurs at the 

Command Unit, the 

GROUND FAULT 

LED will flash on the Command Unit panel. 

f. 

Visual Indicator for Battery Fault 

– 

When a battery fault occurs at the Command Unit, 

the 

BATTERY FAULT 

LED will flash on the Command Unit panel. 

g. 

Visual Indicator for Power Fault 

– 

When a primary power loss occurs at the Command 

Unit, the 

POWER 

LED will disengage on the Command Unit panel. 

2. 

Correcting Faults:

 

a. 

Opens/Shorts on an AOR-CSE Station Cable Run 

– 

Check cable for continuity and 

repair or replace cable. 

b. 

Opens/Shorts on the PSTN/POTS Telephone Line Cable Run 

– 

Check cable for 

continuity and repair or replace cable. 

c. 

System Ground Faults 

– 

Check the Command Unit for proper electrical grounding and 

correct any ground loops. 

d. 

Battery Faults 

– 

Check the voltage level of the backup battery.  Replace the battery if 

the voltage level is low. 

e. 

Power Faults 

– 

Check that primary power is available

—restore primary power. 

3. 

Temporarily Silencing a Fault Condition:

 

Use the 

FAULT RESET 

key switch to silence the audible fault indicator.  The audible alarm will 

be temporarily silenced until the next timed supervisory test occurs (programmable with a 
factory default of every 23 hours).  If the fault remains during the next timed supervisory test, 
the audible alarm will be provided again. 

The LED fault indicators will remain in their trouble condition until the faults have been fully 
corrected. 

4. 

Resetting Fault Condition:

 

When any faults have been corrected, use the 

FAULT RESET 

key switch on the Command 

Unit panel to have it conduct its supervisory tests and clear audible and visual alarms for any 
corrected faults. 

Any faults that have not been corrected will continue to provide a visual alarm.  The audible 
alarm will return on the next timed supervisory test (programmable with a factory default of 
every 23 hours) if the fault is still present.

 

Summary of Contents for AOR-5

Page 1: ...tion or programming of Talkaphone Area of Rescue Call Stations please refer to the manual for the AOR CSE Analog Call Station It is recommended that this instruction set be read completely prior to th...

Page 2: ...ifications Twisted shielded pair specifically designed for use with analog telephones Connect shield to earth ground at the Command Unit Distance ranges for recommended wire gauges are provided in the...

Page 3: ...sorship or affiliation is expressly indicated IV System Overview 1 Local Mode In Local Mode pressing the button on any of the Talkaphone Analog Call Stations will call the AOR 5 AOR 10 Command Unit an...

Page 4: ...rs and does not imply or indicate any approval endorsement sponsorship or affiliation with such owners unless such approval endorsement sponsorship or affiliation is expressly indicated V Internal Sys...

Page 5: ...pective owners and does not imply or indicate any approval endorsement sponsorship or affiliation with such owners unless such approval endorsement sponsorship or affiliation is expressly indicated Fi...

Page 6: ...move the packaged front cover door handle Install the handle onto the outside surface of the latched door using the provided screws Remove the six 6 screws from the stainless steel front panel Careful...

Page 7: ...of the Command Unit Always try to separate power lines from communication lines in order to mitigate the risks of noise or interference on the communication lines A B C D This section outlines the int...

Page 8: ...ating PSTN POTS Telephone Line for Off site Dialing If an analog PSTN POTS telephone line or analog PBX extension line is to be used for off site dialing terminate the analog telephone line or PBX ext...

Page 9: ...E Stations and PSTN Line Carrying out this procedure on the controller board is required for proper open short fault and PSTN POTS telephone line fault detection on the system In the lower right of th...

Page 10: ...d programming to factory defaults Requires prior Master Access Code entry 32 up to 8 digits Programs and stores a new Master Access Code Requires prior Master Access Code entry 33 up to 8 digits Progr...

Page 11: ...or 1 10 Does not require Guard Access Code or Master Access Code entry 4 AOR CSE Station all call when connected through a Sub Command Unit or a remote PSTN call Does not require Guard Access Code or...

Page 12: ...beeps or silence re enter the programming code again If you continue to hear two 2 beeps or silence a second time hang up and try again 3 Remote Mode 1 Pick up a Sub Command Unit handset or remotely c...

Page 13: ...his document or website are the property of their respective owners and does not imply or indicate any approval endorsement sponsorship or affiliation with such owners unless such approval endorsement...

Page 14: ...E Station 4 1 through 5 or 1 through 0 There will be a short pause and then the AOR CSE Station will answer with an open channel microphone and speaker are active 2 Enter the security code 827827 or T...

Page 15: ...website are the property of their respective owners and does not imply or indicate any approval endorsement sponsorship or affiliation with such owners unless such approval endorsement sponsorship or...

Page 16: ...autodial phone number 0 20 digits 03 Fourth autodial phone number 0 20 digits 04 Fifth autodial phone number 6 digits 18 Timing dialing options For further details see Timing Dialing Options for the A...

Page 17: ...r Function Values Definition A Talk Listen Delay Switching time between talk and listen modes i e VOX switching time 1 0 1 seconds 2 0 2 seconds Default 3 0 3 seconds 4 0 4 seconds 5 0 5 seconds 6 0 6...

Page 18: ...ndicating which AOR CSE Station is calling in If a call is already in progress any other calls which come in will cause the appropriate LED to blink to indicate they are awaiting an open line if recor...

Page 19: ...set 3 A prerecorded voice message with physical location information may play at the beginning of the call 4 Answering Calls at a Sub Command Unit 1 When calls are routed to a Sub Command Unit the Sub...

Page 20: ...h on the Command Unit panel f Visual Indicator for Battery Fault When a battery fault occurs at the Command Unit the BATTERY FAULT LED will flash on the Command Unit panel g Visual Indicator for Power...

Page 21: ...ip or affiliation is expressly indicated 5 Primary Power Loss When the Command Unit loses primary power and begins to run on battery backup the POWER LED will disengage or turn off on the Command Unit...

Page 22: ...requires a dedicated telephone line 3 If I forgot the Master Access Code or the programming configuration can I reset the programming on the Command Unit If you have forgotten your Master Access Code...

Page 23: ...may not have been properly terminated inside the Command Unit Verify the internal connections 3 The cabling for the PSTN POTS telephone line or analog PBX extension line may have been disconnected Pl...

Reviews: