54
Page
Operation
Controllers
Built-in controller
Remote controller
7.
Press the
"HOT"
button or
"COLD"
button to select the
time. Press and hold the "HOT" or "COLD" button to
adjust the time more quickly.
NOTICE
: The time is displayed in twenty-four hour clock time.
For example, 11:00 is 11:00 a.m. and 23:00 is 11:00 p.m.
8.
Press the
"PUMP"
button when the desired time flashes
on the display.
The OFF time for PUMP TIMER 2 will flash, indicating that
you can set the end time.
9.
Press the
"HOT"
button or
"COLD"
button to select the
time. Press and hold the "HOT" or "COLD" button to
adjust the time more quickly.
NOTICE
: The time is displayed in twenty-four hour clock time.
For example, 11:00 is 11:00 a.m. and 23:00 is 11:00 p.m.
10.
Press the
"PUMP"
button when the desired time flashes
on the display.
11.
The following steps will set the
temperature drop
that must occur before the recirculation pump will
activate.
Temperature drop below set temp. at which
pump turns on
°F
-10 -15 -20* -25 -30 -35 -40
°C
-6
-8
-11 -14 -17 -19 -22
*The value has been preset at the factory. (Default)
Press the
"HOT"
button or the
"COLD"
button to select
the temperature at which the pump will activate.
12.
Press the
"PUMP"
button on the controller to save your
settings.
Normal Operation
Owner's Guide