PROBLEM
SOLUTIONS
W
ATER HE
ATER
Unit does not ignite
when water goes
through the unit.
•
Is the flow rate over 0.5 GPM (1.9 L/min)? (p. 50)
•
Is the filter on cold water inlet and return connection clean? (p. 63)
•
Check for reverse connection and cross connection.
•
If you use the remote controller and/or built-in controller, is the
power button turned on?
•
Check if the inlet temperature is too high.
The fan motor is
still spinning after
operation has stopped.
•
This is normal. After operation has stopped, the fan motor keeps
running from 15 to 70 seconds in order to re-ignite quickly, as well
as purge all the exhaust gas out of the flue.
Unit sounds abnormal
while in operation
•
Contact the manufacturer at 1-877-737-2840 (USA)
1-888-479-8324 (Canada)
BUIL
T-
IN
C
ONTR
OLLER
AND
REMO
TE
C
ONTR
OLLER
Controller does not
display anything when
the power button is
turned on.
•
Make sure the unit is supplied with power.
•
Make sure the connection to the unit is correct. (pp. 38 and 39)
NOTICE:
When the unit has not operated for five minutes or more, the display
of the controllers turns off to conserve energy.
Although the controller of the parent unit will
display the set
temperature at the Easy-Link System, the controller of the child unit
will not display the set temperature.
An ERROR code is
displayed.
•
Please see pp. 68 and 69.
EAS
Y-LINK
SY
STEM
How are the unit
numbers assigned?
•
For an Easy-Link System, the Parent unit is always labeled #1 and all
other subsequent Child units are numbered randomly.
•
To check which numbers are assigned to which Child units, push
the button on the computer board of any Child unit as shown
below. The unit number will be displayed on the built-in controller
of the Child unit and/or the remote controller of the Child unit, if
installed. (Refer to pp. 40 and 41.)
When the remote
controller turned
ON, STAND BY LED
is lit.
Temperature controller
Troubleshooting
Owner's Guide
Button to check unit numbers
Child units : 540 models