-Pump operation test
-
Operation
Controllers
Built-in controller
Remote controller
1.
Press the ON/OFF button on the controller so the
STAND BY LED turns off.
2.
Press and hold "INFO." and "PUMP" simultaneously
for at least 3 seconds, then the integrated pump
starts operation for 5 minutes.
3.
A segment of the zero (on the right) is lit as follows in clockwise order
during forced pump operation.
4.
The pump will stop operation automatically after five
minutes.
OR
Press the "ON/OFF" button to stop pump operation
test.
Operation
Controllers
Built-in controller
Remote controller
1.
Press the "PUMP" button to start pump operation
and fire the water heater.
2.
"P" and the set temperature are indicated (on the
right) during Manual pump operation.
3.
The pump will stop automatically in five minutes and
the current set temperature and time will be
displayed on the screen.
-Manual pump operation
-
Normal Operation
Owner's Guide
The following procedure will operate the pump. This is useful to verify that the pump is operating prop-
erly and to check the water flow rate.
This operation runs the pump and fire the water heater each time the “PUMP” button is pushed to mini-
mize energy consumption. The pump runs until water temperature at the thermistor inside the water
heater reaches 102 °F (38.9 °C) or the water temperature at the thermistor rises 10 °F (5.6 °C) above the
initial temperature of the water. The pump runs for five minutes at the longest. No. 5 DIP switch of the
lower bank needs to be changed to "ON" position in the operation.
Note:
The pump timer is not available when the No. 5 DIP swtch of the lower bank is set to "ON".