background image

3 of 12 

Variable Speed Injection Pump

 

The PC705-2  uses a pump to inject hot water from the boiler loop into the cool system return water. This pump is operated by the 
PC705-2 at different speeds in order to inject hot boiler water at different rates into the cool system return water. For residential and 
small commercial systems Taco wet rotor circulators are suitable for use as variable speed injection pumps. 

Boiler Loop Pump and a Boiler Supply Sensor

 

The use of a boiler loop pump and boiler supply sensor allows the PC705-2 to regulate the boiler supply water temperature as well 
as the system supply water temperature. If the system supply water temperature approaches a maximum setting, the control can 
back off the speed of the injection pump in order to protect the system. The same also occurs when the boiler supply water 
temperature approaches a minimum boiler setting. 

The rate of response to sudden temperature changes by the variable speed injection system can be typically 2 to 4 times faster 
than by a tempering valve or mixing valve. This faster response provides greater protection for both the system and the boiler. 

PIPING OF VARIABLE SPEED INJECTION SYSTEMS

 

Since mixing by a variable speed injection pump is a relatively new concept, there are a few piping details which should be considered. 

When the injection pump is turned off, there must be no heat 
transfer from the boiler loop to the system loop. In order to 
avoid this unwanted heat transfer, standard primary-second-
ary piping techniques are used as shown in Figure 1. This 
piping arrangement requires that the injection piping be at least 
one pipe diameter smaller than the piping of the boiler and 
system loops. There must be no more than 4 pipe diameters 
between the tees in the boiler and system loops (Note 1) in 
order to prevent ghost flow when the variable speed injection 
pump is off and either the boiler pump or system pump is on. 
Also, there must be at least 6 pipe diameters of straight pipe on 
either side of the tees (Note 2) in order to prevent the momen-
tum of water in the boiler and system loops from pushing flow 
through the injection loop. Finally, there should be a minimum 
1 foot drop to create a thermal trap (Note 3) in order to prevent 
convective heat transfer through the injection loop. 

Design Procedure 

1)  Determine the design operating temperatures of the heating system loop and boiler. (Ts and Tb from figure 1.) 
2)  Determine the flow rate and design temperature drop (

Ts) in the system loop when all zones are turned on. If one of these 

variables is unknown, use Equation 1 or 2 to calculate the other variable. 

3)  Compute Tb - Ts. Look up the flow ratios on Figure 2. 
4)  The design injection flow rate for direct injection is calculated from Equation 3. If the injection flow rate is greater than 45 US GPM, 

it may be necessary to use a 4-way mixing valve instead of a variable speed injection system. 

5)  Decide whether or not to include a balancing valve in the injection piping.  A balancing valve allows adjustment when the injection 

pump is larger than needed.  A balancing valve also provides the possibility of manual operation of the heating system by turning 
the injection pump fully on and adjusting the balancing valve to obtain the desired system supply water temperature. 

6)  The injection piping size and model of pump to install can now be looked up in Figure 3.  Don't oversize the injection system.  If 

the heating system is not able to get enough heat, the boiler's operating temperature can be increased.  This may be done 
automatically by the PC705-2 when the boiler sensor is used. 

Boiler Protection

 

Cool water is often returned to the boiler from low temperature radiant floor heating systems or when the 
heating system is recovering from night setback. This cool boiler return water may cause the boiler to operate 
at such a low temperature that the flue gases condense. Alternatively, when the boiler surfaces are hot due 
to previous loads such as domestic hot water generation, the large temperature difference (

T) between the 

boiler and its return water can cause the boiler to become thermally shocked. Proper protection of the boiler 
under these circumstances requires a modulating mixing device that can temporarily reduce the heating load. 
This is normally accomplished by closing a valve or reducing the speed of an injection pump. 

Maximum System Supply

 

Some systems, such as hydronic radiant floor heating, usually operate at water temperatures that are below 
the minimum boiler supply temperature. This is due to the large surface area of the floors which radiate a 
significant amount of heat at low water temperatures. Floor heating systems also have a maximum floor 
surface temperature limit for occupant health reasons and to protect the materials within the floor. In such 
systems a modulating mixing device is normally required to limit the supply water temperature. 

Mix

Mix

Variable Speed Injection

 

Fig. 1

Balancing

Valve

Boiler

Loop

System

Loop

(Ts)

(Tb)

Variable Speed

Injection Pump

Ts

Tb

=  Boiler supply temperature

Ts

=  System supply temperature

Ts =  System temperature drop (Typically 20

°

F for 

 convectors and 10

°

F for radiant floor heating)

Note 3

Note 1

Note 2

Note 3

Note 1

Note 2

Summary of Contents for PC705-2

Page 1: ...ng system the heat supplied to the building must equal the heat lost by the building The heat supplied to a building is proportional to the temperature of the water and the surface area of the heating element A small surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoo...

Page 2: ...up the flue and reduced boiler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can...

Page 3: ...hen all zones are turned on If one of these variables is unknown use Equation 1 or 2 to calculate the other variable 3 Compute Tb Ts Look up the flow ratios on Figure 2 4 The design injection flow rate for direct injection is calculated from Equation 3 If the injection flow rate is greater than 45 US GPM it may be necessary to use a 4 way mixing valve instead of a variable speed injection system 5...

Page 4: ...the injection pump SYSTEM PUMP OPERATION ThePC705 2hasaninternalsystempumpcontact ThiscontactturnsonwhenthePC705 2hasamixingdemandandisnotinaWWSD The system pump as well as the boiler pump may be controlled by this relay By providing proper flow in the boiler loop the boiler temperature can be accurately controlled based on the mixing load Equation1 System Flow Rate US GPM Design Heating Load Btu ...

Page 5: ... push the front cover onto the enclosure until it snaps into place The variable speed injection pump and system pump wiring terminates in the electrical box All other electri calwiringterminatesinthetwowiringchambersonthe control The wiring is roughed in to the electrical box prior to installation of the control BOILEROPERATION Boiler Sensor Installed WhilethePC705 2hasamixingdemand theboilersuppl...

Page 6: ...T T Zone 4 Zone 3 Zone 2 Zone 1 END SWITCH A Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control ZVC404 EXP END SWITCH B T Boiler Pump Injection Pump Boiler Pump System Pump Injection Pump 120 V ac Outdoor Sensor Boiler Sensor Supply Sensor Priority Zone Switch set to ON DHW Tank T T T T POWER Zone 4 Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control SR 506 EXP...

Page 7: ...3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP Boiler Pump Boiler Pump Injection Pump Injection Pump DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP A Expansion Switch set to Master Mode Switch set to Normal Expansion Switch set to Slave Mode Switch set to Normal PC 705 2 PC 702 1 PC 700 2 DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END ...

Page 8: ...on the Taco Zone Control Ensure the Mode switch on the Zone Control is set to Reset if boiler control is desired orNormalifboilerenableisdesired refertotheBoilerOperationsection Wiring the Sensors Do not apply power to these terminals as this will damage the control OutdoorSensor Connect the two wires from the Outdoor Sensor directly to the Com Out 1 and 3 terminals The Outdoor Sensor measures the...

Page 9: ...F 27 to 107 C The MIX MAX should be set to the maximum temperature allowed in the system loop There are many factors which may limit the allowable supply water temperature in a radiant floor heating slab a few are provided below Nowhere in the concrete should the temperature be maintained above 170 F 77 C The surface temperature of a radiant floor heating slab should normally not exceed 85 F 29 C ...

Page 10: ...mperature Press and release the Item button until the MIX TARGET elements are displayed Boiler Temperature Press and release the Item button until the BOIL element is displayed To view all control settings the Item button may be pressed and held while in the View Menu The contol will then scroll through all the adjustable items MIX Start Use the and buttons to set the desired mixing starting tempe...

Page 11: ...by 5 F 3 C per day If the outdoor temperature is near the WWSD temperature and the rooms are cold increase the MIX Start setting Testing the Sensors A good quality test meter capable of measuring up to 5 000 kΩ 1 kΩ 1000 Ω is required to measure the sensor resistance In addition to this the actual temperature must be measured with either a good quality digital thermometer or if a thermometer is no...

Page 12: ...aged to try to correct the interference by reorienting or relocating the receiving antenna relocating the receiver with respect to this control and or connecting the control to a different circuit from that to which the receiver is connected Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 Fax 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Mississauga On...

Reviews: