background image

4 of 12 

POWERING UP THE CONTROL

 

After the PC705-2 is powered up, all the LCD segments are tuned on for 2 
seconds, followed by a software version number. The control then displays the 
outdoor temperature. 

MIXING DEMAND

 

The PC705-2 obtains a mixing demand through the Taco Zone Control when 
a zone calls for heat. When the PC705-2 receives a mixing demand, the Mixing 
Demand pointer is displayed in the LCD. 

MIXING OPERATION

 

The PC705-2 calculates the required supply water temperature based on the outdoor 
temperature. The supply water temperature is then controlled by varying the speed of an 
injection pump to maintain the target supply temperature. As the heating load increases, 
the PC705-2 speeds up the injection pump and as the load decreases, the PC705-2 slows 
down the injection pump. The bar graph in the bottom of the LCD indicates the speed of 
the variable speed injection. 

Warm Weather Shut Down (WWSD)

 

When the outdoor temperature is warmer than the WWSD setting, the PC705-2 turns 
off the boiler and the variable speed injection pump. The PC705-2 has a freeze 
protection feature that does not allow the supply water temperature to drop below 35

°

(2

°

C) as long as there is a mixing demand signal. 

Maximum System Supply Temperature

 

The PC705-2 has a Maximum Supply setting that can be used to set a maximum system 
supply water temperature. If the supply water temperature approaches the Maximum 
Supply setting, the control reduces the speed of the injection pump. 

SYSTEM PUMP OPERATION

 

The PC705-2 has an internal system pump contact. This contact turns on when the PC705-2 has a mixing demand and is not in a WWSD. 
The system pump as well as the boiler pump may be controlled by this relay. By providing proper flow in the boiler loop, the boiler 
temperature can be accurately controlled based on the mixing load. 

Equation 1 

System Flow Rate (US GPM)  = 

Design Heating Load (Btu/hr) 

500  x  

Ts (

°

F) 

Equation 2 

Ts (

°

F)  = 

    Design Heating Load (Btu/hr) 
500  x  System Flow Rate (US GPM) 

Equation 3 

        Design Injection Flow Rate (US GPM)  = 

System Flow Rate (US GPM)  x  Flow Ratio 

Tb - Ts (

°

F)

Ts (

°

F)

0.40

0.00

0.20

1.00

0.80

0.60

10

30

50

70

90

10

15

20

25

Flow Ratio

20

40

60

80

0.10

0.30

0.50

0.70

0.90

Fig. 2

Taco 007

Taco 007

Taco 007

Taco 007

Taco 007

Taco 007

Taco 007

Taco 0010

Taco 0012

Taco 0012

Taco 0012

Design Injection Flow Rate (US GPM)

Nominal Pipe

Diameter (inches)

TACO

Pump

Without Balancing Valve

4.0

4.5

7.3

9.5

10.0

14.0

23.0

35.0

41.0

45.0

With Balancing Valve

1.5

3.0

3.0

6.0

7.4

8.3

12.0

20.0

31.0

38.5

41.5

0.5

0.5

0.5

0.75

0.75

0.75

1

1.25

1.5

2

2

This table assumes there are 5 feet of pipe, 4 elbows, and 4 branch tees of the listed diameter.

Turns open of the

Balancing Valve (%)

20

100

50

100

100

100

100

100

100

100

100

Fig. 3

Sequence of Operation

 

Outdoor air  temperature

50

(10)

30

(-1)

10

(-12)

-10

(-23)

70

(21)

90

(32)

°

F

(

°

C)

Supply w

ater temper

ature

110

(43)

70

(21)

90

(32)

210

(99)

170

(77)

150

(65)

130

(54)

190

(88)

Maximum System

Supply Setting

Zone 1 Zone 2 Zone 3 Zone 4

POWER

Zone 4

Zone 3

Zone 2

Zone 1

INPUT

120 VOLT CIRCULATORS

END

SWITCH

ZR

X

X

ZC

Mixing

Demand

PC705-2

Start

10 30 50 70 90

% Out

Item

C         US

158033

OUTDR

°

F

VIEW

Summary of Contents for PC705-2

Page 1: ...ng system the heat supplied to the building must equal the heat lost by the building The heat supplied to a building is proportional to the temperature of the water and the surface area of the heating element A small surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoo...

Page 2: ...up the flue and reduced boiler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can...

Page 3: ...hen all zones are turned on If one of these variables is unknown use Equation 1 or 2 to calculate the other variable 3 Compute Tb Ts Look up the flow ratios on Figure 2 4 The design injection flow rate for direct injection is calculated from Equation 3 If the injection flow rate is greater than 45 US GPM it may be necessary to use a 4 way mixing valve instead of a variable speed injection system 5...

Page 4: ...the injection pump SYSTEM PUMP OPERATION ThePC705 2hasaninternalsystempumpcontact ThiscontactturnsonwhenthePC705 2hasamixingdemandandisnotinaWWSD The system pump as well as the boiler pump may be controlled by this relay By providing proper flow in the boiler loop the boiler temperature can be accurately controlled based on the mixing load Equation1 System Flow Rate US GPM Design Heating Load Btu ...

Page 5: ... push the front cover onto the enclosure until it snaps into place The variable speed injection pump and system pump wiring terminates in the electrical box All other electri calwiringterminatesinthetwowiringchambersonthe control The wiring is roughed in to the electrical box prior to installation of the control BOILEROPERATION Boiler Sensor Installed WhilethePC705 2hasamixingdemand theboilersuppl...

Page 6: ...T T Zone 4 Zone 3 Zone 2 Zone 1 END SWITCH A Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control ZVC404 EXP END SWITCH B T Boiler Pump Injection Pump Boiler Pump System Pump Injection Pump 120 V ac Outdoor Sensor Boiler Sensor Supply Sensor Priority Zone Switch set to ON DHW Tank T T T T POWER Zone 4 Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control SR 506 EXP...

Page 7: ...3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP Boiler Pump Boiler Pump Injection Pump Injection Pump DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP A Expansion Switch set to Master Mode Switch set to Normal Expansion Switch set to Slave Mode Switch set to Normal PC 705 2 PC 702 1 PC 700 2 DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END ...

Page 8: ...on the Taco Zone Control Ensure the Mode switch on the Zone Control is set to Reset if boiler control is desired orNormalifboilerenableisdesired refertotheBoilerOperationsection Wiring the Sensors Do not apply power to these terminals as this will damage the control OutdoorSensor Connect the two wires from the Outdoor Sensor directly to the Com Out 1 and 3 terminals The Outdoor Sensor measures the...

Page 9: ...F 27 to 107 C The MIX MAX should be set to the maximum temperature allowed in the system loop There are many factors which may limit the allowable supply water temperature in a radiant floor heating slab a few are provided below Nowhere in the concrete should the temperature be maintained above 170 F 77 C The surface temperature of a radiant floor heating slab should normally not exceed 85 F 29 C ...

Page 10: ...mperature Press and release the Item button until the MIX TARGET elements are displayed Boiler Temperature Press and release the Item button until the BOIL element is displayed To view all control settings the Item button may be pressed and held while in the View Menu The contol will then scroll through all the adjustable items MIX Start Use the and buttons to set the desired mixing starting tempe...

Page 11: ...by 5 F 3 C per day If the outdoor temperature is near the WWSD temperature and the rooms are cold increase the MIX Start setting Testing the Sensors A good quality test meter capable of measuring up to 5 000 kΩ 1 kΩ 1000 Ω is required to measure the sensor resistance In addition to this the actual temperature must be measured with either a good quality digital thermometer or if a thermometer is no...

Page 12: ...aged to try to correct the interference by reorienting or relocating the receiving antenna relocating the receiver with respect to this control and or connecting the control to a different circuit from that to which the receiver is connected Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 Fax 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Mississauga On...

Reviews: