background image

7 of 12 

Reference Applications PC 705-2

 

Drawing 3/705-2: Radiant Floor Heating, High Temperature heating with DHW generation

 

Drawing 4/705-2: Radiant Floor Heating, High Temperature heating with 2 boilers and DHW generation

 

120 V 

(ac)

T

Outdoor

Sensor

T

T

Outdoor

Sensor

Boiler

Sensor

Supply

Sensor

Priority Zone

Switc

set to

 ON

Priority Zone

Switc

set to

 OFF

Boiler

Sensor

(optional)

120 V 

(ac)

T

Outdoor

Sensor

T

T

T

T

T

T

T

Outdoor

Sensor

Boiler

Sensor

Supply

Sensor

Priority Zone

Switc

set to

 ON

Priority Zone

Switc

set to

 OFF

Boiler

Sensor

(optional)

T

T

PO

WER

Zone 3

Zone 2

Zone 1

INPUT

END

SWITCH

ZR

X

X

ZC

Zone 3

Zone 2

Zone 1

T

aco Zone Control SR 503-EXP

Boiler

Pump

Boiler

Pump

Injection

Pump

Injection

Pump

DHW

T

ank

PO

WER

Zone 3

Zone 2

Zone 1

INPUT

END

SWITCH

ZR

X

X

ZC

Zone 3

Zone 2

Zone 1

T

aco Zone Control SR 503-EXP

A

Expansion Switc

h

set to

 Master

Mode Switc

set to

Normal

Expansion Switc

h

set to

 Sla

ve

Mode Switc

set to

Normal

PC

705-2

PC

702-1

PC

700-2

DHW

T

ank

PO

WER

Zone 3

Zone 2

Zone 1

INPUT

END

SWITCH

ZR

X

X

ZC

Zone 3

Zone 2

Zone 1

T

aco Zone Control SR 503-EXP

PO

WER

Zone 4

Zone 3

Zone 2

Zone 1

INPUT

END

SWITCH

ZR

X

X

ZC

Zone 4

Zone 3

Zone 2

Zone 1

T

aco Zone Control SR 506-EXP

Zone 5

Zone 6

Zone 5

Zone 6

A

Expansion Switc

h

set to

 Master

Mode Switc

set to

Reset

Expansion Switc

h

set to

 Sla

ve

Mode Switc

set to

Normal

PC

705-2

*

*

* Same po

w

er 

supply circuit m

ust 

be used

* Same po

w

er 

supply circuit m

ust 

be used

Summary of Contents for PC705-2

Page 1: ...ng system the heat supplied to the building must equal the heat lost by the building The heat supplied to a building is proportional to the temperature of the water and the surface area of the heating element A small surface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoo...

Page 2: ...up the flue and reduced boiler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can...

Page 3: ...hen all zones are turned on If one of these variables is unknown use Equation 1 or 2 to calculate the other variable 3 Compute Tb Ts Look up the flow ratios on Figure 2 4 The design injection flow rate for direct injection is calculated from Equation 3 If the injection flow rate is greater than 45 US GPM it may be necessary to use a 4 way mixing valve instead of a variable speed injection system 5...

Page 4: ...the injection pump SYSTEM PUMP OPERATION ThePC705 2hasaninternalsystempumpcontact ThiscontactturnsonwhenthePC705 2hasamixingdemandandisnotinaWWSD The system pump as well as the boiler pump may be controlled by this relay By providing proper flow in the boiler loop the boiler temperature can be accurately controlled based on the mixing load Equation1 System Flow Rate US GPM Design Heating Load Btu ...

Page 5: ... push the front cover onto the enclosure until it snaps into place The variable speed injection pump and system pump wiring terminates in the electrical box All other electri calwiringterminatesinthetwowiringchambersonthe control The wiring is roughed in to the electrical box prior to installation of the control BOILEROPERATION Boiler Sensor Installed WhilethePC705 2hasamixingdemand theboilersuppl...

Page 6: ...T T Zone 4 Zone 3 Zone 2 Zone 1 END SWITCH A Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control ZVC404 EXP END SWITCH B T Boiler Pump Injection Pump Boiler Pump System Pump Injection Pump 120 V ac Outdoor Sensor Boiler Sensor Supply Sensor Priority Zone Switch set to ON DHW Tank T T T T POWER Zone 4 Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 4 Zone 3 Zone 2 Zone 1 Taco Zone Control SR 506 EXP...

Page 7: ...3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP Boiler Pump Boiler Pump Injection Pump Injection Pump DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END SWITCH ZR X X ZC Zone 3 Zone 2 Zone 1 Taco Zone Control SR 503 EXP A Expansion Switch set to Master Mode Switch set to Normal Expansion Switch set to Slave Mode Switch set to Normal PC 705 2 PC 702 1 PC 700 2 DHW Tank POWER Zone 3 Zone 2 Zone 1 INPUT END ...

Page 8: ...on the Taco Zone Control Ensure the Mode switch on the Zone Control is set to Reset if boiler control is desired orNormalifboilerenableisdesired refertotheBoilerOperationsection Wiring the Sensors Do not apply power to these terminals as this will damage the control OutdoorSensor Connect the two wires from the Outdoor Sensor directly to the Com Out 1 and 3 terminals The Outdoor Sensor measures the...

Page 9: ...F 27 to 107 C The MIX MAX should be set to the maximum temperature allowed in the system loop There are many factors which may limit the allowable supply water temperature in a radiant floor heating slab a few are provided below Nowhere in the concrete should the temperature be maintained above 170 F 77 C The surface temperature of a radiant floor heating slab should normally not exceed 85 F 29 C ...

Page 10: ...mperature Press and release the Item button until the MIX TARGET elements are displayed Boiler Temperature Press and release the Item button until the BOIL element is displayed To view all control settings the Item button may be pressed and held while in the View Menu The contol will then scroll through all the adjustable items MIX Start Use the and buttons to set the desired mixing starting tempe...

Page 11: ...by 5 F 3 C per day If the outdoor temperature is near the WWSD temperature and the rooms are cold increase the MIX Start setting Testing the Sensors A good quality test meter capable of measuring up to 5 000 kΩ 1 kΩ 1000 Ω is required to measure the sensor resistance In addition to this the actual temperature must be measured with either a good quality digital thermometer or if a thermometer is no...

Page 12: ...aged to try to correct the interference by reorienting or relocating the receiving antenna relocating the receiver with respect to this control and or connecting the control to a different circuit from that to which the receiver is connected Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 Fax 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Mississauga On...

Reviews: