28
Description of functions
Pump control functions
Function correspondence table
Series
PW/PWM/PWT
DCLPW/DCLPWM/DCLPWT
CLPW/CLPWM/CLPWT
Model
General chemical injection
High-viscosity
Boiler
High-pressure
Sodium hypochlorite
30R/60R/100R 30/60/100
200
60/100
30R
30
30
30R/60R/100R 30/60/100
Relief-valve function
●
-
-
-
●
-
-
●
-
SAFE mode
●
●
×
●
×
×
×
●
●
Alarm function
●
●
●
●
●
●
●
●
●
ECO mode
●
●
×
●
●
●
●
×
×
✽
× indicates that the function concerned should not be set although it can be set.
!
CAUTION
• When setting the SAFE mode, use the 100% setting for the stroke length. If the stroke length is
changed, the pressure may rise above the rated level.
Safety function selection flow
Prevent the occurrence of abnormal pressure levels.
YES
START
SAFE mode
SAFE mode
Alarm function
+
YES
NO
YES
A discharge pressure of 0.7 MPa or more is required.
Relief-valve function
Alarm function*
NO
NO
YES
Displays and outputs an alarm when trouble has occurred.
* Displayed and output during blocked operation.
SAFE mode
When the SAFE mode is enabled, the force of the pumped chemical liquid is controlled during a blocked operation to
prevent the pressure from rising.
It is recommended that the SAFE mode be set when using only the pressure of the anti-siphonal check valve or at
other times when the pump is used at a low pressure.
If the “P-03 Blocked operation” parameter is enabled when the SAFE mode is enabled, an alarm is displayed and out-
put at a pressure level that is lower than normal.
ECO mode
When the ECO mode is enabled, the power-on time is
automatically reduced in accordance with the variations
in the discharge pressure, and the power consumption
is reduced.
✽
When the ECO mode is enabled for the DCLPW
or CLPW
, it becomes harder to vent the air so use
‘disabled’ as the ECO mode setting.
20
18W
8W
1.0MPa
0.1MPa
15
10
5
0
Power consum
p
tion
(W
)
ex. PW-60 (300strokes/min)
08-32̲EM-127̲PW(E).indd 28
2014/11/17 11:43:58