D200-100-00
9
I56-3888-005
#
PARAMETER
PARAMETER
RANGE
SA LB
DESCRIPTION
COMMENTS
82 Monday is holiday
YES/NO
Allows use of different alarm and pre-
alarm levels on one or more days of the
week
NO: Device will change between day and
night settings at selected times (if
Parameter 81 set) .
YES: Night settings are always used
83 Tuesday is holiday
YES/NO
84 Wednesday is holiday
YES/NO
85 Thursday is holiday
YES/NO
86 Friday is holiday
YES/NO
87 Saturday is holiday
YES/NO
88 Sunday is holiday
YES/NO
89 Sensor 1 day alarm
level
1 . .9
Day and night pre-alarm and alarm level
settings .
90 Sensor 2 day alarm
level
1 . .9
91 Sensor 1 day pre-alarm
level
1 . .9
92 Sensor 2 day pre-alarm
level
1 . .9
93 Sensor 1 night alarm
level
1 . .9
94 Sensor 2 night alarm
level
1 . .9
95 Sensor 1 night pre-
alarm level
1 . .9
96 Sensor 2 night pre-
alarm level
1 . .9
97 Alarm mode
Sensor Mode,
Module Mode
Sets the method used to indicate an
alarm .
SENSOR MODE: When remote output on
a sensor is set ON for configured time,
that sensor channel goes into alarm .
When the remote output turns OFF, the
channel stops signalling alarm .
MODULE MODE: When the Output
Activate command is sent to a channel
module, that channel goes into alarm . To
exit alarm, an Output Deactivate
command must be sent .
Note that the Output Activate
command will not set an alarm in
Sensor Mode, and turning on the
sensor remote output will not set an
alarm in Module Mode .
Note that when in Module Mode, an
alarm is not latched .
In common chamber (2 sensor)
version – the Sensor Mode is
required to enable the AND/OR
option .
98 Sensor communication
timeout
0 (Not Used),
1…240 s
The device will give a sensor
communication fault when a sensor is
inactive for this period of time .
Inactive means that sensor remote
output is OFF and it is not blinking .
99 Remote output time for
alarm
50, 100,...10000ms
The device will go to alarm if the sensor
remote output is ON at least for this time .
Not applicable when Alarm Mode is
set to Module Mode .