D200-100-00
6
I56-3888-005
A1: FAAST LT CONFIGURATION PARAMETERS
All the FAAST LT configurable parameters are described in Table
A1 below . The default values set into the unit at manufacture are
listed in Tables A2 and A3. The user can change parameter values
using the PipeIQ™ application software that runs on a PC and
then upload the new configuration into the unit.
SA denotes a Stand Alone unit
LB is a Loop Based (addressable) unit
A
a
denotes applicable
APPENDIX A
FAAST LT CONFIGURATION PARAMETERS AND DEFAULT SET-UP VALUES
Table A1: FAAST LT Configuration Parameters
#
PARAMETER
PARAMETER
RANGE
SA LB
DESCRIPTION
COMMENTS
1
Maintenance Password
1111 - 9999
4 digit code required to enable front panel
push buttons and access Maintenance
mode .
Factory default password 3111.
2
Current configuration
number
0..255
Number used to identify the current device
configuration . Every time the configuration is
changed, this number is incremented .
Factory default is 1 .
When 255 is reached the
number rolls back to 0
3
Current configuration
date
DD/MM/YY
HH:MM:SS
Date/Time of last device configuration
upload .
4
Channel 1 enabled
YES/NO
YES: Channel is enabled and operating as a
smoke detector .
NO: Channel is disabled .
Only possible with 2 channel
units; cannot disable both
channels at the same time .
5
Channel 2 enabled
YES/NO
6
Sensor 1 enabled
YES/NO
YES: Sensor is enabled and operating as a
smoke detector .
NO: Sensor is disabled
For 1 c 2 sensor version
only; not possible to disable both
sensors .
7
Sensor 2 enabled
YES/NO
8
Daylight saving enabled YES/NO/AUTO
Allows the real time clock date to change for
a daylight saving period (+1 hour)
NO: Daylight saving off . YES:
period is specified by parameters
9 and 10.
AUTO: sets start date to last
Sunday in March and end date
to last Sunday in October .
9
Daylight saving start
date
DD/MM HH:MM
Start date/time of daylight saving period
Used when daylight saving is set
to YES .
10 Daylight saving end
date
DD/MM HH:MM
End date/time of daylight saving period
11 Disable time
1..240 min
When disabled the device stops reporting
alarms and faults for this period .
When the time expires or
RESET is pressed, device
returns to Normal state .
12 Maintenance timeout
1..30 min or 0 (Not
Used)
Sets the period of inactivity after which a unit
will return to Normal from Maintenance
mode
In remote maintenance (USB
connected) there is no device
timeout .
13 Trend log interval
1..240 min or 0 (Not
Used)
Time interval used by a device to regularly
record its status .
Events are also logged as they
occur .
14 Sensors blinking
replicated
YES/NO
NO: No blink
YES: Channel alarm LED blinks green when
the detector is in Normal state .
When channel is in alarm, the
alarm LED will change to red .
15 Both supplies monitored YES/NO
NO: Only power supply #1 input is
monitored .
YES: Power supply #2 is also monitored
16 Common chamber
sensors required for
alarm
1,2
Detector alarm logic for common chamber
model (1 channel x2 sensors):
1 . OR function – either sensor in alarm
2 . AND function – both sensors need to be
in alarm .
If a sensor is disabled or in fault,
this parameter is ignored .
17 Sounder automatic cut-
off time
0 (Not Used),
5,10,15,…,600 s
Sounders turn off after this time period,
following activation .