D200-100-00
10
I56-3888-005
A2: FAAST LT DEFAULT SET-UP VALUES
All the default value settings are listed in the following two tables .
Table A2 refers to Stand Alone units, whilst Table A3 refers to Loop
Based (addressable) units .
X
means that a parameter is not applicable .
* value set to Italian time zone at manufacture .
Table A2: Stand Alone Versions
#
PARAMETER
PARAMETER RANGE
1 Channel
1 Sensor
1 Channel
2 Sensor
2 Channel
2 Sensor
1
Maintenance Password
1111 - 9999
3111
3111
3111
2
Current configuration number
0..255
1
1
1
3
Current configuration date
DD/MM/YY
HH:MM:SS
* * *
4
Channel 1 enabled
YES/NO
YES
YES
YES
5
Channel 2 enabled
YES/NO
X
X
YES
6
Sensor 1 enabled
YES/NO
YES
YES
YES
7
Sensor 2 enabled
YES/NO
X
YES
YES
8
Daylight
saving
enabled YES/NO/AUTO
NO NO NO
9
Daylight saving start date
DD/MM HH:MM
25/02 02:00
25/02 02:00
25/02 02:00
10 Daylight saving end date
DD/MM HH:MM
28/10 02:00
28/10 02:00
28/10 02:00
11 Disable time
1..240 min
60
60
60
12 Maintenance timeout
1..30 min or 0 (DISABLED)
5
5
5
13 Trend log interval
1..240 min or 0 (DISABLED)
0
0
0
14 Sensors blinking replicated
YES/NO
YES
YES
YES
15 Both supplies monitored YES/NO
NO NO NO
16 Number of sensors required in
alarm
1,2
1 1 1
17 Sounder automatic cut-off time
0 (Disabled), 5,10,15,…,600 s
0
0
0
18 Channel 1 alarm is latched
YES/NO
YES
YES
YES
19 Channel 2 alarm is latched
YES/NO
YES
YES
YES
20 Alarm delay
0 ..240 s
0
0
0
21 Auxiliary relay is used for channel 2
faults
YES/NO
YES YES YES
22 Channel 1 label
16 char (ASCII code from 32 to 127)
“1”
“1”
“1”
23 Channel 2 label
16 char (ASCII code from 32 to 127)
X
X
“2”
24 Channel 1 fan speed mode
Manual, Auto
Auto
Auto
Auto
25 Channel 2 fan speed mode
Manual, Auto
X
X
Auto
26 Channel 1 manual fan speed
0..10
X
X
X
27 Channel 2 manual fan speed
0..10
X
X
X
28 Reference flow for channel 1
32 – 65 litres/min
45 litres/min
45 litres/min
45 litres/min
29 Reference flow for channel 2
32 – 65 litres/min
X
X
45 litres/min
30 High flow threshold for channel 1
Internal Setting
set to EN54-20 requirements ( -20% - +20%)
31 High flow threshold for channel 2
Internal Setting
X
X
As Above
32 Low flow threshold for channel 1
Internal Setting
set to EN54-20 requirements ( -20% - +20%)
33 Low flow threshold for channel 2
Internal Setting
X
X
As Above
34 Flow fault delay
0..240 s
60
60
60
35 Channel 1 filter due date
DD/MM/YY
01/01/99
01/01/99
01/01/99
36 Channel 2 filter due date
DD/MM/YY
X
X
01/01/99
37 General fault is latched
YES/NO
NO
NO
NO
38 General fault delay
0..240 s
60
60
60
39 Pressure
68758 – 110000 Pa
101325
101325
101325
40 Power restart alert time
0
(Alert disabled
), 1..240 s,
255 (no time limit)
0
0
0
41 Auxiliary relay set on low/high
temperature alert
YES/NO
NO NO NO
42 Auxiliary relay set on external input
in not normal state
YES/NO
NO NO NO
43 Auxiliary relay set on low power
alert / high power fault
YES/NO
NO NO NO