D200-100-00

7

I56-3888-005

#

PARAMETER

PARAMETER

RANGE 

SA LB

DESCRIPTION 

COMMENTS

18  Channel 1 alarm is 

latched 

YES/NO 

NO: When alarm condition is reached, the 

device activates the alarm relay . When the 

alarm condition is removed the alarm relay is 

deactivated . 

YES: When alarm condition is reached, the 

device activates the alarm relay . When the 

alarm condition is removed the alarm relay 

remains set until the device is reset . 

19  Channel 2 alarm is 

latched 

YES/NO 

20  Alarm delay 

0..240 s 

When alarm condition is reached, a delay 

period can be introduced before the alarm is 

activated . 

If the detector alarm condition is 

removed before activation, the 

delay is reset . 

21  Auxiliary relay is used 

for channel 2 faults 

YES/NO 

NO: Device faults are reported on the fault 

relay; this relay is common on 2 channel 

units .  

YES, the AUX relay will separately report 

CH2 faults; CH1 faults continue to be 

reported on the fault relay . Common faults 

will be reported by both relays . 

Faults common to both channel 

are, for example, ASD EEPROM 

fault, external input fault, etc . 

22  Channel 1 label 

16 character (ASCII 

code from decimal 

32 to 127) 

Provides a label to name a channel in free 

text . 

Example: "Building A" "Building 

B" 

23  Channel 2 label 

16 character (ASCII 

code from decimal 

32 to 127) 

24  Channel 1 fan speed 

mode 

Manual, Auto 

Selects the fan speed control mode 

The optimal flow though the 

device is about 45 litres/minute. 

Typically, this is equivalent to 

fan speed 5 . 

Low and high flow limits are set 

to meet the EN54 requirements. 

A flow fault is given if the flow 

goes out of the -20% and +20% 

of the reference flow range. 

In Auto mode, following 

initialization, the unit sets the 

fan speed to reach the reference 

flow programmed in the device. 

In Manual mode, the user can 

set the fan speed. 

Use PipeIQ LT to change default 

configuration of the reference 

flow (both modes) and fan 

speed (manual mode). 

25  Channel 2 fan speed 

mode 

Manual, Auto 

26  Channel 1 manual fan 

speed 

1..10 

Defines the fan speed in manual mode . 

27  Channel 2 manual fan 

speed 

1..10 

28  Reference flow for 

channel 1 

32 – 65 litres/min 

This value represents the correct flow level 

to maintain . 

29  Reference flow for 

channel 2 

32 – 65 litres/min 

30  High flow threshold for 

channel 1 

Internal Setting 

High flow threshold 

31  High flow threshold for 

channel 2 

Internal Setting 

32  Low flow threshold for 

channel 1 

Internal Setting 

Low flow threshold 

33  Low flow threshold for 

channel 2 

Internal Setting 

34  Flow fault delay 

0..240 s 

A delay can be set to stop reporting a flow 

fault for a defined period .  

If the fault condition is removed 

before activation of a fault, the 

delay will be reset . 

35  Channel 1 filter due date  DD/MM/YY 

Date to clean air filters . When date is 

reached, the device will give a filter fault . 

36  Channel 2 filter due date  DD/MM/YY 

37  General fault is latched 

YES/NO 

NO: The general fault relay is activated 

when a fault is present and will reset when 

the fault is removed .  

YES: The general fault relay is activated 

when a fault is present . When the fault 

condition is removed the relay remains set 

until a device reset . 

38  General fault delay 

0..240 s 

A delay can be set to stop reporting a 

general fault for a defined period .  

If the fault condition is removed before 

activation of a fault, the delay will be reset . 

39  Pressure 

68758 – 110000 Pa 

Not used . 

 

40  Power restart alert time 

0 (Not Used), 1..240 

s,

255 (no time limit) 

When the device is switched on, it can give 

a power on alert . The time period for this 

alert signal can be set by the user . 

Summary of Contents for FAAST LT

Page 1: ...control parameters from a PC running the proprietary software application PipeIQ Version 2 3 and above This manual describes how to monitor and configure the various operating parameters available in...

Page 2: ...ice is in Normal the Service Mode state is entered automatically when the front cover is opened The FAAST LT unit switches off the power to the unit Once the service action is complete and the front c...

Page 3: ...purposes only Manually setting the fan speed to change the air flow will not alter the associated hi lo flow limit settings in the FAAST LT unit Therefore this option should not be used to set or cha...

Page 4: ...el 6 0 50 obs ft 1 64 obs m Level 7 1 00 obs ft 3 28 obs m Level 8 1 50 obs ft 4 92 obs m Level 9 2 00 obs ft 6 56 obs m To set these levels ensure the Configuration tab is selected in the left pane a...

Page 5: ...ions see the PipeIQ Help Menu PipeIQ Help The online help is a guide through the PipeIQ application The Help opens in a separate window where it is possible to search and navigate to information on di...

Page 6: ...r 2 enabled YES NO 8 Daylight saving enabled YES NO AUTO Allows the real time clock date to change for a daylight saving period 1 hour NO Daylight saving off YES period is specified by parameters 9 an...

Page 7: ...t sets the fan speed to reach the reference flow programmed in the device In Manual mode the user can set the fan speed Use PipeIQ LT to change default configuration of the reference flow both modes a...

Page 8: ...ated by external input Note that only one action can be selected at a time Note External input only active in NORMAL state 50 External input silences sounders YES NO 51 External input resets device YE...

Page 9: ...ethod used to indicate an alarm SENSOR MODE When remote output on a sensor is set ON for configured time that sensor channel goes into alarm When the remote output turns OFF the channel stops signalli...

Page 10: ...YES 19 Channel 2 alarm is latched YES NO YES YES YES 20 Alarm delay 0 240 s 0 0 0 21 Auxiliary relay is used for channel 2 faults YES NO YES YES YES 22 Channel 1 label 16 char ASCII code from 32 to 12...

Page 11: ...MI 17 00 17 00 17 00 60 Holiday day 1 date DD MM empty empty empty DD MM empty empty empty 79 Holiday day 20 date DD MM empty empty empty 80 Sounder activation mode On Pre alarm On Alarm Alarm Alarm A...

Page 12: ...32 to 127 X X 2 24 Channel 1 fan speed mode Manual Auto Auto Auto Auto 25 Channel 2 fan speed mode Manual Auto X X Auto 26 Channel 1 manual fan speed 0 10 X X X 27 Channel 2 manual fan speed 0 10 X X...

Page 13: ...Sounder activation mode On Pre alarm On Alarm X X X 81 Day night mode enabled YES NO X X X 82 Monday is holiday YES NO X X X 83 Tuesday is holiday YES NO X X X 84 Wednesday is holiday YES NO X X X 85...

Page 14: ...t X X User can configure a specific delay between fault condition and fault indication 0 240 s Fault F013 HIGH FLOW FAULT CH1 Channel 1 flow is over the configured limit X X User can configure a speci...

Page 15: ...feet X Please clean the sensor Alert A009 COMPENSATION 0 6 DIRTY ALERT S1 The sensor 1 chamber is very dirty 0 6 feet X Please clean the sensor Alert A010 DRIFT LIMIT ALERT S1 The sensor 1 chamber is...

Page 16: ...2 2 2 3 2 4 2 5 2 6 2 5 2 5 7 8 9 2 5 10 2 5 FAN SPEED 10 2 5 11 12 13 2 5 14 3 15 3 16 3 17 3 5 18 3 5 3 5 END 4 4 Example Pipe Configuration 1 Channel Single Pipe 100m x 18 Holes Class C Hole 2 Hol...

Page 17: ...ing 5 10 10 10 10 10 10 5 4 8 75m 0 2 75m HOLE SIZE mm 1 2 5 2 2 5 3 2 5 4 3 5 3 6 3 7 3 8 3 9 3 10 3 11 12 13 14 15 16 17 18 END END HOLE Typical Example Pipe Configuration 1 Channel T Piece 2 Pipes...

Page 18: ...Configuration 1 Channel Single Pipe With Filter Class C FILTER HOLE SIZE mm 1 3 5 2 4 3 3 4 3 5 3 5 END 3 5 Hole 4 Hole 3 Hole 2 Hole 1 5 3 5 6 7 3 5 6 Hole 6 6 6 6 6 Hole 7 6 6 End hole FAN SPEED 6 3...

Page 19: ...D200 100 00 19 I56 3888 005 System Sensor Europe Pittway Tecnologica S r l Via Caboto 19 3 34147 TRIESTE Italy http www systemsensoreurope com...

Reviews: