D200-100-00
15
I56-3888-005
FAULT /
ALERT
SHORT NAME
DESCRIPTION
SA
LB
NOTES
Alert [A005]
LOW
TEMPERATURE
ALERT
Device temperature is
under the limit .
X X
Alert [A006]
LOW POWER
ALERT
Device supply voltage is
under 21 V (nominal) .
X
X
Check the voltage . Changing the FAAST LT unit
parameter, it is possible to monitor either the main or
both power supplies
Alert [A007]
POWER RESTART
ALERT
Device was not powered
for an unknown period of
time .
X
X
Given after every POWER ON .
This alert can be disabled, given only for a defined
time or it can be latched depending on the
configuration .
In SA version, alert time has to be longer than the time
for sensors to become stable (45 s).
Alert [A008]
COMPENSATION
0.3% DIRTY ALERT
S1
The sensor 1 chamber is
dirty . The sensor software
has tried to
compensate but a high
value has been reached
(0.3 %/feet).
X
Please clean the sensor .
Alert [A009]
COMPENSATION
0.6% DIRTY ALERT
S1
The sensor 1 chamber is
very dirty (0.6 %/feet).
X
Please clean the sensor .
Alert [A010]
DRIFT LIMIT ALERT
S1
The sensor 1 chamber is
very dirty and has reached
the maximum level
allowed .
X
Please clean the sensor .
Alert [A011]
FILTER ALERT CH1 Filter 1 due date reached .
X
X
Alert [A012]
COMPENSATION
0.3% DIRTY ALERT
S2
The sensor 2 chamber is
dirty . The sensor software
has tried to
compensate but a high
value has been reached
(0.3 %/feet).
X
Please clean the sensor .
Alert [A013]
COMPENSATION
0.6% DIRTY ALERT
The sensor 2 chamber is
very dirty (0.6 %/feet).
X
Please clean the sensor .
Alert [A014]
DRIFT LIMIT ALERT
S2
The sensor 2 chamber is
very dirty and has reached
the maximum level
allowed .
X
Please clean the sensor .
Alert [A015]
FILTER ALERT CH2 Filter 2 due date reached .
X
X
Alert [A016]
LED PCB ERROR
Bad communication with
LED pcb .
X
X
Please check connection .
Note: when unit has PCB error, user can enter
MAINTENANCE mode, opening front cover (no
password is needed)