D200-100-00

15

I56-3888-005

FAULT / 

ALERT 

SHORT NAME 

DESCRIPTION

SA

LB

NOTES 

Alert [A005] 

LOW

TEMPERATURE

ALERT

Device temperature is 

under the limit . 

X X  

Alert [A006] 

LOW POWER 

ALERT

Device supply voltage is 

under 21 V (nominal) .  

Check the voltage . Changing the FAAST LT unit 

parameter, it is possible to monitor either the main or 

both power supplies 

Alert [A007] 

POWER RESTART 

ALERT

Device was not powered 

for an unknown period of 

time .

Given after every POWER ON .  

This alert can be disabled, given only for a defined 

time or it can be latched depending on the 

configuration .

In SA version, alert time has to be longer than the time 

for sensors to become stable (45 s). 

Alert [A008] 

COMPENSATION 

0.3% DIRTY ALERT 

S1

The sensor 1 chamber is 

dirty . The sensor software 

has tried to 

compensate but a high 

value has been reached 

(0.3 %/feet). 

 

Please clean the sensor . 

Alert [A009] 

COMPENSATION 

0.6% DIRTY ALERT 

S1

The sensor 1 chamber is 

very dirty (0.6 %/feet). 

 

Please clean the sensor . 

Alert [A010] 

DRIFT LIMIT ALERT 

S1

The sensor 1 chamber is 

very dirty and has reached 

the maximum level 

allowed .  

 

Please clean the sensor . 

Alert [A011] 

FILTER ALERT CH1  Filter 1 due date reached . 

 

Alert [A012] 

COMPENSATION 

0.3% DIRTY ALERT 

S2

The sensor 2 chamber is 

dirty . The sensor software 

has tried to 

compensate but a high 

value has been reached 

(0.3 %/feet). 

 

Please clean the sensor . 

Alert [A013] 

COMPENSATION 

0.6% DIRTY ALERT 

The sensor 2 chamber is 

very dirty (0.6 %/feet). 

 

Please clean the sensor . 

Alert [A014] 

DRIFT LIMIT ALERT 

S2

The sensor 2 chamber is 

very dirty and has reached 

the maximum level 

allowed .  

 

Please clean the sensor . 

Alert [A015] 

FILTER ALERT CH2  Filter 2 due date reached . 

 

Alert [A016] 

LED PCB ERROR 

Bad communication with 

LED pcb .

Please check connection . 

Note: when unit has PCB error, user can enter 

MAINTENANCE mode, opening front cover (no 

password is needed) 

Summary of Contents for FAAST LT

Page 1: ...control parameters from a PC running the proprietary software application PipeIQ Version 2 3 and above This manual describes how to monitor and configure the various operating parameters available in...

Page 2: ...ice is in Normal the Service Mode state is entered automatically when the front cover is opened The FAAST LT unit switches off the power to the unit Once the service action is complete and the front c...

Page 3: ...purposes only Manually setting the fan speed to change the air flow will not alter the associated hi lo flow limit settings in the FAAST LT unit Therefore this option should not be used to set or cha...

Page 4: ...el 6 0 50 obs ft 1 64 obs m Level 7 1 00 obs ft 3 28 obs m Level 8 1 50 obs ft 4 92 obs m Level 9 2 00 obs ft 6 56 obs m To set these levels ensure the Configuration tab is selected in the left pane a...

Page 5: ...ions see the PipeIQ Help Menu PipeIQ Help The online help is a guide through the PipeIQ application The Help opens in a separate window where it is possible to search and navigate to information on di...

Page 6: ...r 2 enabled YES NO 8 Daylight saving enabled YES NO AUTO Allows the real time clock date to change for a daylight saving period 1 hour NO Daylight saving off YES period is specified by parameters 9 an...

Page 7: ...t sets the fan speed to reach the reference flow programmed in the device In Manual mode the user can set the fan speed Use PipeIQ LT to change default configuration of the reference flow both modes a...

Page 8: ...ated by external input Note that only one action can be selected at a time Note External input only active in NORMAL state 50 External input silences sounders YES NO 51 External input resets device YE...

Page 9: ...ethod used to indicate an alarm SENSOR MODE When remote output on a sensor is set ON for configured time that sensor channel goes into alarm When the remote output turns OFF the channel stops signalli...

Page 10: ...YES 19 Channel 2 alarm is latched YES NO YES YES YES 20 Alarm delay 0 240 s 0 0 0 21 Auxiliary relay is used for channel 2 faults YES NO YES YES YES 22 Channel 1 label 16 char ASCII code from 32 to 12...

Page 11: ...MI 17 00 17 00 17 00 60 Holiday day 1 date DD MM empty empty empty DD MM empty empty empty 79 Holiday day 20 date DD MM empty empty empty 80 Sounder activation mode On Pre alarm On Alarm Alarm Alarm A...

Page 12: ...32 to 127 X X 2 24 Channel 1 fan speed mode Manual Auto Auto Auto Auto 25 Channel 2 fan speed mode Manual Auto X X Auto 26 Channel 1 manual fan speed 0 10 X X X 27 Channel 2 manual fan speed 0 10 X X...

Page 13: ...Sounder activation mode On Pre alarm On Alarm X X X 81 Day night mode enabled YES NO X X X 82 Monday is holiday YES NO X X X 83 Tuesday is holiday YES NO X X X 84 Wednesday is holiday YES NO X X X 85...

Page 14: ...t X X User can configure a specific delay between fault condition and fault indication 0 240 s Fault F013 HIGH FLOW FAULT CH1 Channel 1 flow is over the configured limit X X User can configure a speci...

Page 15: ...feet X Please clean the sensor Alert A009 COMPENSATION 0 6 DIRTY ALERT S1 The sensor 1 chamber is very dirty 0 6 feet X Please clean the sensor Alert A010 DRIFT LIMIT ALERT S1 The sensor 1 chamber is...

Page 16: ...2 2 2 3 2 4 2 5 2 6 2 5 2 5 7 8 9 2 5 10 2 5 FAN SPEED 10 2 5 11 12 13 2 5 14 3 15 3 16 3 17 3 5 18 3 5 3 5 END 4 4 Example Pipe Configuration 1 Channel Single Pipe 100m x 18 Holes Class C Hole 2 Hol...

Page 17: ...ing 5 10 10 10 10 10 10 5 4 8 75m 0 2 75m HOLE SIZE mm 1 2 5 2 2 5 3 2 5 4 3 5 3 6 3 7 3 8 3 9 3 10 3 11 12 13 14 15 16 17 18 END END HOLE Typical Example Pipe Configuration 1 Channel T Piece 2 Pipes...

Page 18: ...Configuration 1 Channel Single Pipe With Filter Class C FILTER HOLE SIZE mm 1 3 5 2 4 3 3 4 3 5 3 5 END 3 5 Hole 4 Hole 3 Hole 2 Hole 1 5 3 5 6 7 3 5 6 Hole 6 6 6 6 6 Hole 7 6 6 End hole FAN SPEED 6 3...

Page 19: ...D200 100 00 19 I56 3888 005 System Sensor Europe Pittway Tecnologica S r l Via Caboto 19 3 34147 TRIESTE Italy http www systemsensoreurope com...

Reviews: