STYLITIS-10 

 

INSTALLATION 

GUIDE 

 

Summary of Contents for Stylitis-10

Page 1: ...STYLITIS 10 INSTALLATION GUIDE ...

Page 2: ...ELAY DRIVING BY A DIGITAL OUTPUT 41 20 SOLAR PANEL CONNECTION 44 21 LOGGER QUICK CHECK 45 22 CONNECTION EXAMPLE 46 Copyright 1998 2016 The Symmetron Company Updated May 2016 No part of this publication may be reproduced stored in a retrieval system or transmitted in any form by any means without the prior written permission of Symmetron Company Information furnished by Symmetron is believed to be ...

Page 3: ... logger comes equipped with two serial ports Communication speed fixed at 9600 baud with 8 data bits 1 stop bit and no parity bit The ports are full duplex and their usage is the following PERIPHERAL always active DB9 Plug Female PIN 2 Transmit PIN 3 Receive PIN 5 Ground It is useful for a connection to a standard PC s serial port A straight type cable is required i e one which connects pin 2 of o...

Page 4: ... are recommended Connect the shield to the GROUND screw Do not connect the shield to the anemometer IN CASE IT DOESN T WORK Check that the anemometer rotates freely and that its axle is straight With a multimeter check the resistance in the anemometer s terminals It must be less than 1000Ω and greater than 400Ω Rotate the anemometer and measure the AC voltage on its terminals it should generate at...

Page 5: ...lso change the units by clicking the UNITS line The Slope and Offset are automatically updated again In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough ΝΟΤΕ For calibrated anemometers you can enter the correct SLOPE και OFFSET values in retrospect Connect...

Page 6: ...is the black one while connect the red one as well to the 12V power supply BAT Ext Typical wire size 2 x 0 25 mm2 shielded cables are recommended Connect the shield to the GROUND screw and the metal body of the anemometer if plastic leave it unconnected IN CASE IT DOESN T WORK Check that the anemometer or rain gauge rotates freely and that its axle is straight With a multimeter check the resistanc...

Page 7: ... the SENSOR line and select 40H or A100R The channel type first line along with the Slope Offset are automatically updated You can also change the units by clicking the UNITS line The Slope and Offset are automatically updated again Connect serially via Opton 4 Connect the computer s COM port to the datalogger s PERIPHERAL port Before changing the setup select ACQ OFF After changing setup select A...

Page 8: ...ΟΤΕ For calibrated anemometers or rain gauges you can enter the correct SLOPE και OFFSET values in retrospect 4 NRG MAX 40 ANEMOMETER CONNECTION Connect the first anemometer to screws 1 CH1 and 2 GND on the left screw terminal Connect the second anemometer to screws 6 CH8 and 5 GND on the right screw terminal If you are using a datalogger with Serial Number starting with 026A connect a 20kΩ pull u...

Page 9: ...wing Typical wire size 2 x 0 25 mm2 shielded cables are recommended Connect the shield to the GROUND screw and the metal body of the anemometer CH1 Cin Dout GND CH2 Ain Din Dout CH3 Ain Din Dout GND CH4 Ain Din Dout V Pulsed Out AUX ΑΡΙΣΤΕΡΗ ΚΛΕΜΑ 1 2 3 4 5 6 7 8 CH5 Ain Din Dout GND CH6 Ain Din Dout CH7 Ain Din Dout GND CH8 Ain Din Dout BAT Ext GND BAT Ext ΔΕΞΙΑ ΚΛΕΜΑ 1 2 3 4 5 6 7 8 IN CASE IT D...

Page 10: ...e is straight Rotate the anemometer and measure the DC voltage between the COUNTER input and GND it should toggle between 0 and 5 Volts approximately 1 2 3 4 5 6 7 8 LEFT SCREW TERMINAL GND CH2 Ain Din Dout CH3 Ain Din Dout GND CH4 Ain Din Dout V Pulsed Out AUX CH1 Cin Dout 1 2 3 4 5 6 7 8 RIGHT SCREW TERMINAL GND CH6 Ain Din Dout CH7 Ain Din Dout GND CH8 Ain Din Dout BAT Ext GND BAT Ext CH5 Ain D...

Page 11: ...its by clicking the UNITS line The Slope and Offset are automatically updated again In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough ΝΟΤΕ For calibrated anemometers you can enter the correct SLOPE και OFFSET values in retrospect Connect serially via Opt...

Page 12: ...are recommended Connect the shield to the GROUND screw and the metal body of the anemometer SETUP See chapter 3 REED ANEMOMETER IN CASE IT DOESN T WORK Check that the anemometer rotates freely and that its axle is straight Rotate the anemometer and measure the DC voltage between the COUNTER input and GND it should toggle between 0 and 5 Volts approximately 1 2 3 7 8 SIG GND BAT HZG HZG THIES FIRST...

Page 13: ...rew of the wind vane to a GROUND position Typical wire size 2 x 0 25 mm2 shielded cables are recommended If a shield exists connect it to the GROUND screw Do not connect the shield to the wind vane Be careful not to short circuit the shield with any of the wind vane screws Wrong connections my damage the wind vane IN CASE IT DOESN T WORK Check that the wind vane rotates freely and that its axle is...

Page 14: ...where you wish for the vane zero mark to be For more details see the note below In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough ΝΟΤΕ Enter the vane offset for direction measurement in degrees 0 359 For instance if the vane zero mark is placed 30 east t...

Page 15: ...ed wires to 3 CH2 and 8 AUX of the left screw terminal Connect PT100 s red wires along with the cable s shield if there is one to 5 GND of the left screw terminal You can connect two or more ΡΤ100 this way but to save wires prefer the connection shown in the next page Wire polarity is irrelevant Typical wire size 4 x 0 25 mm2 shielded cables are recommended If a shield exists connect it to the GND...

Page 16: ... line along with the Slope Offset are automatically updated You can also change the units by clicking the UNITS line The Slope and Offset are automatically updated again In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough MEASURE SENSOR Temperature Externa...

Page 17: ...isconnected from the logger use a multimeter to check the resistance between the sensor s terminals At ambient temperature 23 C it should be about 110Ω PT100 RTD 1 PT100 RTD 2 PT100 RTD 3 1 2 3 4 5 6 7 8 LEFT SCREW TERMINAL GND CH2 Ain Din Dout CH3 Ain Din Dout GND CH4 Ain Din Dout V Pulsed Out AUX CH1 Cin Dout 1 2 3 4 5 6 7 8 RIGHT SCREW TERMINAL GND CH6 Ain Din Dout CH7 Ain Din Dout GND CH8 Ain ...

Page 18: ...s in the table below The channel type first line along with the Slope Offset are automatically updated You can also change the units by clicking the UNITS line The Slope and Offset are automatically updated again In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end i...

Page 19: ...0 kΩ 0 1 3ppm type Wire sizes in the following table can then be reduced to one tenth 1 10 or cables can be up to 10 times longer Wire polarity is irrelevant Wire size according to connection distance shielded cables are recommended CABLE LENGTH meters WIRE SIZE mm2 PT100 Up to 1 2x0 35 Up to 2 2x0 50 Up to 3 2x0 75 Up to 4 2x1 Up to 5 2x1 5 Up to 10 2x2 5 Up to 20 2x4 If a shield exists connect i...

Page 20: ...ternal Thermos_PT100 OR Thermos_PT1000 OR Thygro_Temperature Sensor PT1000 etc Temperature Internal PT100_ element Temperature Submersed PT100_probe Temperature Surface PT100_patch The channel type first line along with the thermometer s type PT100 and the input s gain by default the measurement is full scale 200 850 C are automatically updated In this case you cannot change the units only C is av...

Page 21: ...ALLATION GUIDE 0516 21 In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough ...

Page 22: ...6 4 CH7 and 5 GND on the right screw terminal Wire polarity does matter see drawing The sensor connects to an external 7V 30VDC power source typically a 12V lead acid battery The sensor GND together with the cable shield connects to a logger GND position Typical wire size 4 x 0 25 mm2 shielded cables are recommended SCREW V dc 12V SCREW V t TEMPER SCREW V RH HUMIDITY SCREW GND GROUND TEMPHUMIDSENS...

Page 23: ...ect HD9009TR _T P6312_T or HMP50 1V_out _T The channel type first line along with the Slope Offset are automatically updated You can also change the units by clicking the UNITS line The Slope and Offset are automatically updated again ΝΟΤΕ For calibrated sensors you can enter the correct SLOPE και OFFSET values in retrospect IN CASE IT DOESN T WORK Connect the sensor to the battery With a multimet...

Page 24: ... P6312_H or HMP50 1V_out _H The channel type first line along with the Slope Offset are automatically updated In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough ΝΟΤΕ For calibrated sensors you can enter the correct SLOPE και OFFSET values in retrospect ...

Page 25: ...rawing The clear wire of the sensor connects to screw 3 GND The pyranometer s shield wire together with the cable s shield is connected to CH2 Typical wire size 2 x 0 25 mm2 shielded cables are recommended WITHOUT AMPLIFIER WITH AMPLIFIER IN CASE IT DOESN T WORK With a multimeter check the voltage between screws 8 and 9 the sensor output should be about 12mV 1000W m 2 In the dark it should display...

Page 26: ...fier The channel type first line along with the Slope Offset are automatically updated You can also change the units by clicking the UNITS line The Slope and Offset are automatically updated again In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough ΝΟΤΕ Fo...

Page 27: ... APMLIFIER WITH AMPLIFIER SETUP Similarly to the previous chapter s sensor The only difference is that in the SENSOR line select SKS 1110 or SKS 1110 Pyranometer Amp IN CASE IT DOESN T WORK With a multimeter check the voltage between screws 8 and 9 the sensor output should be about 100mV 1000W m 2 In the dark it should display less than 1W SKS 1110 1 2 3 4 5 6 7 8 LEFT SCREW TERMINAL GND CH2 Ain D...

Page 28: ...00mV 1000W m 2 In the dark it should display less than 1W CMP6 1 2 3 4 5 6 7 8 LEFT SCREW TERMINAL GND CH2 Ain Din Dout CH3 Ain Din Dout GND CH4 Ain Din Dout V Pulsed Out AUX CH1 Cin Dout 1 2 3 4 5 6 7 8 LEFT SCREW TERMINAL GND CH2 Ain Din Dout CH3 Ain Din Dout GND CH4 Ain Din Dout V Pulsed Out AUX CH1 Cin Dout BAT Ext right screw terminal CMP6 OUT CH B Symmetron OUT CH A IN CH B Pyranometer Ampli...

Page 29: ...pyranometers so that they can output a 0 2 5V or a 0 5V signal therefore they need power supply 5 24V The Slope Offset are automatically updated but for calibrated sensors you can change them in retrospect 14 OTHER USED ANALOG SENSORS CONNECTION AND SETUP SELECTION IN THE MEASURE LINE SELECTION IN THE SENSOR LINE MANUFA CTURER BAT Ext Analog pin eg CH2 GND Humidity External YGRO SYMMETRON Red Wire...

Page 30: ...crew terminal The black wire of the sensor connects to an analog channel only For connection of other sensors depth sensors and pH sensors and their setup see the table below ATTENTION Always connect the sensors without external power supply IN CASE IT DOESN T WORK Make sure that the ANALOG input is configured as current and that the VA PULSED output is setup for 12V or 18V With the sensor connect...

Page 31: ... order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough ΝΟΤΕ For calibrated sensors you can enter the correct SLOPE και OFFSET values in retrospect Connect serially via Opton 4 Connect the computer s COM port to the datalogger s PERIPHERAL port Before changing t...

Page 32: ... matter see drawing The Tiltometer connects to an external 6V 15VDC power source typically a 12V lead acid battery The sensor GROUND together with the cable shield connects to a logger GROUND position Typical wire size 4 x 0 25 mm2 shielded cables are recommended SCREW V dc 12V SCREW V t ELEVATION SCREW V RH AZIMUTH SCREW GND GROUND TILTOMETER 1 2 3 4 5 6 7 8 LEFT SCREW TERMINAL GND CH2 Ain Din Do...

Page 33: ...ck the MEASURE line and select Elevation Angle Click the SENSOR line and select Tiltometer_Elevation_2 5V The channel type first line along with the Slope Offset are automatically updated Connect serially via Opton 4 Connect the computer s COM port to the datalogger s PERIPHERAL port Before changing the setup select ACQ OFF After changing setup select ACQ ON to start acquisition data logging ...

Page 34: ... Angle Click the SENSOR line and select Tiltometer_Azimuth_2 5V The channel type first line along with the Slope Offset are automatically updated In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough ...

Page 35: ... Connect the second sensor s open collector output to screws 6 CH8 and 5 GND on the right screw terminal Wire polarity does matter See the diagrams on the side of each sensor Below you can see connection examples of a 1 phase sensor and a 3 phase one 1 PHASE EXAMPLE 1RCEM1 3 PHASE EXAMPLE 1RCETM63 SETUP Connect serially via Opton 4 Connect the computer s COM port to the datalogger s PERIPHERAL por...

Page 36: ...along with the Slope Offset are automatically updated You can also change the units by clicking the UNITS line The Slope and Offset are automatically updated again In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to change the setup of multiple channels one Write Setup in the end is enough 18 VOLTAGE AND CURRENT SENSORS AC Voltag...

Page 37: ...nd the end to pin 3 see the corresponding figures below Given that all sensors above will have a 0 5VDC output However this output must be converted to 0 2 5V suitable for Stylitis 10 via an external voltage divider Suggested value for the divider s resistors is 1 15KΩ Connect the divider s output to an analog channel CH2 CH8 You do not need to connect it to pin 7 as well but it helps to screw all...

Page 38: ...or 0 2 5V out DC Voltage sensor 4 20mA out AC Voltage sensor 4 20mA out SETUP Connect serially via Opton 4 Connect the computer s COM port to the datalogger s PERIPHERAL port Before changing the setup select ACQ OFF After changing setup select ACQ ON to start acquisition data logging ...

Page 39: ...If you have selected Voltage_DC before click the Sensor field and select a sensor shown in the screen shot above which have a 0 5V output except for the None one each one of which is suitable for a specific measurement and has a specific output as you can see in their description If you have selected Voltage_AC the corresponding sensors will appear The channel type first line along with the Slope ...

Page 40: ...h has a 0 5V output which is suitable for a specific measurement and has a specific output as you can see in their description If you have selected Current_AC the corresponding sensors will appear The channel type first line along with the Slope Offset are automatically updated In order to save the changes click Write Setup in the Setup tab in the Data logger online bar on the left If you wish to ...

Page 41: ...a current lower than 20mA the max current the logger s digital output can supply Such a relay can receive at its output at the NC NO contacts a direct DC voltage of 24V at 2A or an alternating voltage of 110V at 1A Besides the voltage limit there is a power limit as well ie for instance for a 12VDC load a 4ADC current can pass through the contacts If the voltage and current through this small rela...

Page 42: ... you wish to satisfy your conditions For instance channel 2 measures temperature see chapter 8 and controls the digital output eg channel 8 Connect serially via Opton 4 Connect the computer s COM port to the datalogger s PERIPHERAL port Before changing the setup select ACQ OFF After changing setup select ACQ ON to start acquisition data logging ...

Page 43: ...n create a combination of ANDs and ORs which if satisfied the output becomes low the switch closes By clicking an AND line you may give a value to the control channel You may click the channel to select it and the comparison operator to select above below between or not between Finally click the value to type the one you wish In order to save the changes click Write Setup in the Setup tab in the D...

Page 44: ...each one is connected to the Charge Regulator via a diode EXTERNAL LEAD ACID BATTERY 12V OR POWER SUPPLY 8 28Vdc BLACK RED SOLAR PANEL 12V CHARGE REGULATOR YELLOW BLACK SOLAR PANEL 12V SOLAR PANEL 12V DIODES 3Α 100V 1N5402 YOU CAN PARALLEL BATTERIES OF SAME TYPE VOLTAGE AND CAPACITY USE ONE 4 5A CHARGE REGULATOR FOR 40W TOTAL SOLAR PANEL POWER ...

Page 45: ... 2 ANALOG INPUT CHECK Select Read Inputs Setup in the Setup tab in the Data logger online bar on the left commands group Setup Set channels CH2 CH8 as analog voltage inputs 0 2500mV with SLOPE 1 0 and OFFSET 0 0 Connect the V Pulsed out voltage output to the analog input you want to test Select Read data from the command group Data Correct value for the analog input you are checking is 2 5V 3 COUN...

Page 46: ...TYLITIS 10 INSTALLATION GUIDE 0516 46 22 CONNECTION EXAMPLE ANEMOMETER WIND VANE TEMP SENSOR HORIZONTAL BOOM 100cm LOGGER SHELTER BOX 50Χ40Χ20cm MAST BASE CABLES VERTICAL BOOM 60cm 3 STRAPS FOR EACH BOOM ...