STYLITIS-10 INSTALLATION GUIDE [0516]
18
SETUP:
Click ’Read Inputs Setup’ in the ‘Setup’ tab, in the ‘Data logger online’ bar on the left
Open nodes: CH2 (which will bind CH3 as well), CH4 (which will bind CH5 as well),
and/or CH6 (which will bind CH7 as well).
Click the MEASURE line and select
‘Temperature External’ ‘Temperature Internal’,
‘Temperature Submersed’ or ‘Temperature Surface’, according to if the temperature
measurement will be internal, external, etc.
Each measurement type affords the corresponding current excitation PT100 sensor,
in a differential input setup. Eg, if you have selected
‘Temperature Submersed’
before, click the SENSOR line and select
‘PT100_probe_CurrentExc_Diff’. For this
connection, select one combination from the ones in the table below.
The channel type (first line), along with the Slope, Offset are automatically updated.
You can also change the units by clicking the UNITS line. The Slope and Offset are
automatically updated again.
In order to save the changes, click
‘Write Setup’ in the ‘Setup’ tab, in the ‘Data logger
online’ bar on the left. If you wish to change the setup of multiple channels, one
‘Write Setup’ in the end is enough.
MEASURE
SENSOR
Temperature External Thermos_PT100_CurrentExc_Diff OR
Thermos_PT1000_CurrentExc_Diff, OR
Thygro_Temperature Sensor(PT1000)_CurrentExc_Diff, etc
Temperature Internal
PT100_ element _CurrentExc_Diff
Temperature
Submersed
PT100_probe_CurrentExc
Temperature Surface
PT100_patch_CurrentExc_Diff
Connect serially via Opton 4. (Connect the
computer’s COM port to the datalogger’s
PERIPHERAL port).
Before changing the setup select:
ACQ OFF
.
After changing setup select:
ACQ ON
to start acquisition (data logging).