STYLITIS-10 INSTALLATION GUIDE [0516]
20
SETUP:
Click
’Read Inputs Setup’ in the ‘Setup’ tab, in the ‘Data logger online’ bar on the left
Open
an analog channel’s node (e.g. CH2).
Click the MEASURE line and select
‘Temperature External’ ‘Temperature Internal’,
‘Temperature Submersed’ or ‘Temperature Surface’, according to if the temperature
measurement will be internal, external, etc.
Each measurement type affords the corresponding voltage excitation PT100 sensor.
Eg, if you have selected
‘Temperature Submersed’ before, click the SENSOR line
and select
‘PT100_probe’. For this connection, select one combination from the ones
in the table below.
MEASURE
SENSOR
Temperature External
Thermos_PT100 OR Thermos_PT1000, OR
Thygro_Temperature Sensor(PT1000), etc
Temperature Internal
PT100_ element
Temperature Submersed
PT100_probe
Temperature Surface
PT100_patch
The channel
type (first line), along with the thermometer’s type (PT100) and the
input’s gain (by default the measurement is full scale (-200…850
°
C)
)
are
automatically updated.
In this case, you cannot change the units (only
°C is available). However, you can
change the gain by clicking on the channel’s first line and select ‘RTD Temperature’
and then a different gain. You can also select PT1000 instead of PT100, by clicking
the last line of the channel (see the figure below).
Connect serially via Opton 4. (Connect the
computer’s COM port to the datalogger’s
PERIPHERAL port).
Before changing the setup select:
ACQ OFF
.
After changing setup select:
ACQ ON
to start acquisition (data logging).