STYLITIS-10 INSTALLATION GUIDE [0516]
3
1.
GENERAL
INPUTS:
Stylitis-10 is able to measure voltage, frequency and pulses (and current as an
option). With suitable sensors it is also capable of measuring:
Wind speed, direction and wind-turbine power curves
Temperature, humidity, pressure.
Solar radiation, rain height, water speed, etc.
The sensors’ output must be within 0~2.5V (or 0~5V in the Stylitis-10/5 version)
and 0~5kHz.
OUTPUTS:
The vane supply output (+V PULSED) (2.5V for Stylitis-10 and 5V for Stylitis-
10/5) may be used for excitation, as they are capable of supplying up to a TOTAL
of 20milliAmps with an accuracy of 0.2%.
Similarly, the current excitation output (AUX) (0.5mA) is also pulsed and it can
supply PT-100 thermometers, etc with an accuracy of 6%.
SERIAL PORT:
The Data logger comes equipped with two serial ports. Communication speed
fixed at 9600 baud with 8 data bits, 1 stop bit and no parity bit. The ports are full
duplex and their usage is the following:
PERIPHERAL (always active)
DB9 Plug (Female). PIN 2: Transmit, PIN 3 Receive, PIN 5 Ground. It is useful for
a connection to a standard PC’s serial port. A "straight" type cable is required, i.e.
one, which connects pin 2 of one connector to pin 2 of the other, etc. The cable
connector to the datalogger must be male, while the PC’s connector must be
female.
COMMUNICATION (it is activated only when the communication module
is EXTERNAL- set it via Opton software)
DB9 Plug (Male). PIN 2: Receive, PIN 3 Transmit, PIN 5 Ground. It is useful for
connection to an external modem’s serial port. A "straight" type cable is required,
i.e. one, which connects pin 2 of one connector to pin 2 of the other, etc. The
cable connector to the datalogger must be female, while the one to the modem
depends on the modem.