5 : 61
Service
ModBus-register W3 applies to software after 0.76
Holding
register
16 bit integer register
R/W
Modbus
Name
Min/Max
Remarks
Default
4x0037
Normal flow EA
0/100
(%)
50
4x0038
Economy flow SA
0/100
(%)
20
4x0039
Economy flow EA
0/100
(%)
20
4x0040
Night cool flow SA
50/100
(%)
80
4x0041
Night cool flow EA
50/100
(%)
80
4x0042
Boost flow SA
0/100
(%)
90
4x0043
Boost flow EA
0/100
(%)
90
4x0044
Not used
4x0045
Not used
4x0046
Stand-by flow EA
0/100
(%)
10
4x0047
Stand-by flow EA
0/100
(%)
10
4x0048
P term Heat
10/10000
Scale 1:100
5000
4x0049
I term Heat
10/10000
Scale 1:100
10
4x0050
P term Cool
10/10000
Scale 1:100
5000
4x0051
I term Cool
10/10000
Scale 1:100
10
4x0052
P term Change over
10/10000
Scale 1:100
5000
4x0053
I term Change over
10/10000
Scale 1:100
50
4x0054
SA 0% value
0/5000
0
4x0055
SA 100% value
5000/10000
10000
4x0056
EA 0% value
0/5000
0
4x0057
EA 100% value
5000/10000
10000
4x0058
Not used
4x0059
Not used
4x0060
Not used
4x0061
Not used
4x0062
Not used
4x0063
Manual Temp
0-50
(degC) Only used in Manual state
4x0064
Manual SA flow
0/100
(%) Only used in Manual state
4x0065
Manual EA flow
0/100
(%) Only used in Manual state
4x0066
Not used
4x0067
Not used
4x0068
Not used
4x0069
Copy of Coil Status 1-16
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
…
Bit15=0x0016"
Summary of Contents for CONDUCTOR W1