5 : 44
Service
Display image
Description
P_1119
16 C
Room unit’s min temperature
min
0
max 20
Indicates which lowest
temperature is possible to
adjust manually on the room
unit in the MAN operating
mode.
P_1120
28 C
Room unit’s max temperature
min
25
max 50
Indicates which highest
temperature is possible to
adjust manually on the room
unit in the MAN operating
mode.
P_1121
20 C
Night cool temp set point
min
10
max 20
Indicates the temperature
setpoint applicable to the Night
cool function.
P_1122
480
RU back to auto state
min
0
max 1200
Indicates how long after the
most recent manual room
temperature adjustment that
the controller should return to
the AUTO mode.
0 = Not used
P_1123
3500
P term Cooling Scale 1:100
min
1
max 10000
Indicates the value for P for
cooling. A high value denotes
faster control. A low value
denotes slower control
P_1124
10
I term Cooling Scale 1:100
min
1
max 10000
Indicates the value for I for
cooling. A high value denotes
faster control. A low value
denotes slower control.
P_1125
3500
P term Heating Scale 1:100
min
1
max 10000
Indicates the value for P for
heating. A high value denotes
faster control. A low value
denotes slower control.
P_1126
10
I term Heating Scale 1:100
min
1
max 10000
Indicates the value for I for
heating. A high value denotes
faster control. A low value
denotes slower control.
P_1127
23
TC_Normal
min
15
max 30
Switch in cooling for normal
operation.
P_1128
21
TH_Normal
min
15
max 30
Switch in heating for normal
operation.
P_1129
25
TC_Economy
min
10
max 30
Switch in cooling for economic
operation
P_1130
19
TH_Economy
min
10
max 30
Switch in heating for economic
operation.