5 : 56
Service
ModBus-register W1 applies to software after 0.76
Input register 16 bit integer register
Read only
Modbus
Name
Min/Max
Remarks
Default
3x0001
Component Name ID
0/10
ID for type of controller in Conductor and
Wise system
00003
3x0002 - 0017
Component Name
0/999
Name built of max 16 chr, exch chr (ASCII
standard)
0
3x0018
Application ID
3x0019
HW Serial No.
3x0020
SW version
3x0021
Not used
3x0022
Application state
0/8
0=Init, 1=Auto Normal, 2=Auto Economy,
3=Manual, 4=Stand-by, 5=Emengency,
6=NightCool
3x0023
Not used
3x0024
Not used
3x0025
Time since last boot (Year)
3x0026
Time since last boot (Hours)
0/8760
After 8760h Year is updated
3x0027
Time since last boot (Minutes)
0/60
After 60min Hour is updated
3x0028
Temp sensor regulator
Cels. Scaling 1:10
3x0029
Temp sensor RU1
Cels. Scaling 1:10
3x0030
Temp sensor RU2
Cels. Scaling 1:10
3x0031
Temp set point RU
Setpoint in regulator form parameter or
Room Unit
3x0032
Not used
3x0033
Battery level RU
Volts. Scaling 1:10
3x0034
Not used
3x0035
Not used
3x0036
Not used
3x0037
Input Analog 1
0/10000
(mV)
3x0038
Input Analog 2
0/10000
(mV)
3x0039
Input Analog 3
0/10000
(mV)
3x0040
Input Analog 4
0/10000
(mV)
3x0041
Output PWM 1
0/100
(%)
3x0042
Output PWM 2
0/100
(%)
3x0043
Output PWM 3
0/100
(%)
3x0044
Output PWM 4
0/100
(%)
3x0045
Output Analog 1
0/10000
(mV)
3x0046
Output Analog 2
0/10000
(mV)
3x0047
Output Analog 3
0/10000
(mV)
3x0048
Output Analog 4
0/10000
(mV)
3x0049
PID Water Out
-100/100
(%)
3x0050
PID ChangeOver Out
-100/100
(%)
3x0051
Not used
3x0052
Not used
3x0053
Cool Water
0/100
(%)
3x0054
Warm Water
0/100
(%)
3x0055
Not used
3x0056
Not used