Service
Application parameters W1
Application parameters are parameter-specific for the selected application.
Display image
Description
P_1101
4
System1=H,2=C,3=ChOv,4=HC
min
1
max 4
Indicates how the climate
system should operate for
heating and cooling.
1 = Heating only
2 = Cooling only
3 = Change-over function
4 = Heating/Cooling
P_1102
1
0=ext.temp, 1 or 2 room units
min
0
max 2
Indicates whether one or
two room units are used. If 2
units are used they should be
connected with a cable.
0 = The controllers temp.
sensor is used, 1 = 1 unit
2 = 2 units
P_1103
10
C
Frost guard temp.
min
5
max 12
Indicates at which temperature
the frost protection should
switch in.
P_1108
1
Economy mode available
min
0
max 1
Indicates whether the Economy
mode is available.
0 = No
1 = Yes
P_1109
1
ActuatorCool 1=NC, 2=0-10V, 3=NO
min
1
max 3
Indicates which sort of valve
actuator is installed in the
cooling water circuit
(1=24V-NC, 2=0-10V, 3=24V-
NO)
P_1110
1
ActuatorHeat 1=NC, 2=0-10V, 3=NO
min
1
max 3
Indicates which sort of valve
actuator is installed in the
heating water circuit..
(1=24V-NC, 2=0-10V, 3=24V-
NC)
P_1111
0
Window 0=NP
min
0
max 0
Indicates whether a window
contact is installed and if so
how it is installed.
0 = No contact installed
P_1112
0
Occupancy 0=NP
min
0
max 0
Indicates whether a presence
detector is installed and if so
how it is installed.
0 = No contact installed
P_1113
5000
P term Change over
min
1
max 10000
Indicates the value for P for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
P_1114
50
I term Change over
min
1
max 10000
Indicates the value for I for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.