5 : 59
Service
ModBus-register W3 applies to software after 0.76
Input Status
Discrete Input (1 bit)
Read only
Modbus
Name
Min/Max
Remarks
Default
1x0031
Radio chip broken
0/1
ALARM, requires HW reset
1x0032
Parameter file revision
0/1
ALARM, requires HW reset
1x0033
Parameter file format
0/1
ALARM, requires HW reset
1x0034
No ModBus ID
0/1
ALARM, requires HW reset
1x0035
No Application
0/1
ALARM, requires HW reset
1x0036
No parameters
0/1
ALARM, requires HW reset
1x0037
Parameter missing
0/1
ALARM, requires HW reset
1x0038
Parameter value error
0/1
ALARM, requires HW reset
1x0039
Parameter file size
0/1
ALARM, requires HW reset
1x0040
Wrong parameter file
0/1
ALARM, requires HW reset
1x0041
Check Duct Group SM
0/1
ALARM, resets after right parameters
1x0042
Check Duct Group DC
0/1
ALARM, resets after right parameters
1x0043
Previous parameters are lost
0/1
ALARM, requires HW reset
1x0044
Factory parameters take up
0/1
ALARM, requires HW reset
1x0045
Not used
1x0046
Not used
1x0047
No supply pressure from AHU
0/1
ALARM, resets automatically
1x0048
No exhaust pressure from AHU
0/1
ALARM, resets automatically
1x0049
Supply duct 100% open
0/1
ALARM, resets automatically
1x0050
Exhaust duct 100% open
0/1
ALARM, resets automatically
1x0051
Low voltage detect
0/1
ALARM, resets automatically
1x0052
Not used
1x0053
Duct group member missing
0/1
ALARM, resets automatically
1x0054
Negative pressure
0/1
ALARM, resets automatically