Interfaces of the Device
P Line Maritim HMI
44
4.4.1.2
Cable
The maximum cable length depends on the data transfer rate used.
4.4.1.3
Termination
Terminate the CAN bus at both ends by terminating resistors (120 Ohm).
NOTICE
A shielded twisted-pair cable complying with ISO 11898-2 must be used.
A suitable cable with the designation „SAC-5P- 2,0-920/FS SCO“ is offerd by
Phoenix Contact GmbH with article number 1518216.
Table 4-11 Bit rate CAN
Bit rate
Cable length
125 kBit/s
500 m
500 kBit/s
100 m
1 MBit/s
40 m
The switch positions for ON or OFF are printed onto the operating device. Only
the specified switch positions are allowed.
Table 4-12 Termination switch CAN
Switch position
Function
ON
Termination (120 Ohm)
OFF
No termination