Installation and Commissioning
P Line Maritim HMI
24
2.3.2
Grounding
The grounding is performed - depending on the type of device - with a slip-on
sleeve (noiseless ground / functional earth ground) or a ring cable lug (protective
ground).
1. Strip approx. 5 mm (0.197") off the wires.
2. Fit the stripped wires - depending on the type of device - with a slip-on sleeve
or a ring cable lug.
3. Plug the slip-on sleeve on the flat tab or mount the ring cable lug with the nut
to the threaded bolt.
Figure 2-15 Noiseless ground / protective ground
NOTICE: Damage
A separate copper conductor must always be provided for the grounding. The
conductor must have a minimum cross-section of 1.5 mm² (16 AWG) and must
be kept as short as possible.
You must adhere to a maximum torque of 1 Nm at an protective grounding on
the threaded bolt.
Summary of Contents for TPEM070ZGW
Page 6: ...Overall Table of Contents M Line Maritim HMI 6...
Page 32: ...Control and Display Elements P Line Maritim HMI 32...
Page 48: ...Interfaces of the Device P Line Maritim HMI 48...
Page 52: ...Maintenance and Servicing P Line Maritim HMI 52...
Page 74: ...Ordering Data P Line Maritim HMI 74...
Page 76: ...76...
Page 77: ......