14
3.6 Clearances to Combustibles
Refer to Figure 3-7, Figure 3-6, Table 3-2 and Table 3-3 for clearances to combustibles of the FLAIR insert.
Table 3-2: Clearances to Combustibles
Note that the non-combustible hearth must
extend a minimum of 16
” for USA (406 mm) and
18
’’ (457 mm) for Canada from the front of the
door
and 8” (203mm) on each side of the
masonry fireplace opening.
WARNING: Keep a
minimum distance of 5’ (152 cm) from the
unit to any combustible material (such as
firewood, furniture, and drapes) as a fire
hazard precaution.
The depth of the mantle is measured from the
face of the fireplace door. When the non-
combustible wall is recessed, the depth of the
mantle can be increased by the amount of the
recess.
Note that a mantel cannot be installed
below the minimum clearance of 13
” from the
bottom of the mantel to the top edge of the
door.
Table 3-3: Examples of Depth of Mantle with Respect to Distance from Top Edge of Door
6
6
Values determined using a 45
o
rule
– 1 inch of height added results in 1 inch additional allowable depth
Sidewall from outer edge of fuel door
15.5
” (394 mm)
Side trim
(max 4” depth) from outer
edge of fuel door
7
” (178 mm)
Protruding mantel (max 8
” depth)
from top edge of fuel door
13
” (330 mm)
Height (H) from the base of the unit
to the floor with a non-compliant
N.F.P.A.
211
hearth
extension
having a negligible R-value
13” (330 mm)
Height (H) from the base of the unit
to the floor with a non-compliant
N.F.P.A.
211
hearth
extension
having a R-value of 2.957
USA: 3.5’’ (89 mm)
CAN: 1.25’’ (32
mm)
Maximum
mantle depth
Distance from the top edge
of the door of the FLAIR to
the bottom of the mantle
8
” (203 mm)
13
” (330 mm)
10
” (254 mm)
15
” (381mm)
12
” (305 mm)
17
” (432 mm)
Figure 3-8: Clearances to Combustibles (a) Front View (b) Side View