TROUBLESHOOTING

Continued

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

ODS/pilot lights but fl ame goes 
out when control knob is released

1.  Control knob not fully pressed 

in

2.  Control knob not pressed in 

long enough

3.  Safety  interlock  system  has 

been triggered

4.  Equipment shutoff valve not 

fully open

5.  Pilot fl ame not touching ther-

mocouple, which allows ther-
mocouple  to  cool,  causing 
pilot  flame  to  go  out.  This 
problem  could  be  caused  by 
one or both of the following:

  A) Low gas pressure
  B)  Dirty  or  partially  clogged 

ODS/pilot 

6.  Thermocouple  connection 

loose at control valve 

7.  Thermocouple damaged
8.  Control valve damaged

1.  Press in control knob fully

2.  After  ODS/pilot  lights,  keep 

control  knob  pressed  in  30 
seconds

3.  Wait  one  minute  for  safety 

interlock  system  to  reset. 
Repeat ignition operation

4.  Fully open equipment shutoff 

valve

5.  A)  Contact  local  natural  or 

propane/LP gas company

  B) Clean ODS/pilot 

(see Clean-

ing  and  Maintenance, 

Page 

27

)

  or  replace  ODS/pilot  as-

sembly

6.  Hand tighten until snug, then 

tighten 1/4 turn more

7.  Replace pilot assembly
8.  Replace control valve

Burner does not light after ODS/
pilot is lit

1.  Inlet gas pressure is too low
2.  Burner orifi ce is clogged

3.  Thermopile leads disconnect-

ed or improperly connected

4.  Burners will not come on in 

remote position

1.  Contact local natural or pro-

pane/LP gas company

2.  Clean  burner 

(see  Cleaning 

and  Maintenance, 

Page  27

)

 

or replace burner orifi ce

3.  Reconnect leads 

(see Wiring 

Diagram, 

Page 28

)

4.  Replace battery in hand-held 

remote and receiver

Delayed ignition of burner

1.  Manifold pressure is too low

2.  Burner orifi ce is clogged

1.  Contact local natural or pro-

pane/LP gas company

2.  Clean  burner 

(see  Cleaning 

and  Maintenance, 

Page  27

)

 

or replace burner orifi ce

Burner  backfiring  during 
combustion

1.  Burner  orifi ce  is  clogged  or 

damaged

2.  Damaged burner
3.  Gas regulator defective
4.  Inlet gas pressure is too low

1.  Clean  burner 

(see  Cleaning 

and  Maintenance, 

Page  27

)

 

or replace burner orifi ce

2.  Replace damaged burner
3.  Replace gas regulator
4.  Contact local natural or pro-

pane/LP gas company

Summary of Contents for VCM3026ZMN

Page 1: ...ch it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on Page 7 of this manual WARNING If the information in th...

Page 2: ...Safety Standards and are listed by PFS TECO to ANSI Z21 11 2 as unvented Gas fired room heaters This appliance may be installed in an aftermarket permanently located manufactured mobile home where not...

Page 3: ...rial other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Fireplace front and screen become very hot when running fire...

Page 4: ...create a white powder residue within burner box or on adjacent walls or furniture 10 This fireplace needs fresh air ventilation to run properly This fireplace has an Oxygen Depletion Sensing ODS safe...

Page 5: ...the Commonwealth of Massachusetts The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a T handle type valve Unvented applian...

Page 6: ...til installation has been completed 2 Cut two plastic straps to remove the log from the firebox cavity 3 Anoptionalblowerisavailable SeeAccessories Page 34 Install optional blower now Follow installat...

Page 7: ...ound window and door frames between sole plates and floors between wall ceiling joints between wall panels at penetrations for plumbing electrical and gas lines and at other openings If your home meet...

Page 8: ...ct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors Example Gas water appliance ____________ Btu Hr Gas firebox logs ___________ Btu Hr Total __________...

Page 9: ...ion grills or ducts You must provide two permanent open ings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors or spaces open to the outdoors The...

Page 10: ...e in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventilation Page 7 NOTE Your fireplace is designed to be used in zero clearanceinst...

Page 11: ...8 Page 12 for the rough opening The height is 26 7 8 which is the same as the wall opening above 2 If installing GA3450TA blower accessory do so at this time Follow instructions included with blower a...

Page 12: ...ible materials such as wall board gypsum board sheet rock drywall plywood etc may be butted up next to the sides and top edge of the firebox Combustible materials should never overlap the firebox fron...

Page 13: ...hearth base to run gas line to fireplace see Figure 11 Make sure to locate access hole so cabinet mantel will cover it when installed NOTE You can secure base to floor using wood screws Countersinksc...

Page 14: ...lign fireplace in mantel assembly so the trim overlaps mantel evenly on all three sides 12 Lower bottom louver door Use 3 wood screws provided with mantel accessory to attach fire place to base see ma...

Page 15: ...rd out of the cabinet by inserting it through the bushing on the outer casing see Figure 16 Page 16 Plug fan kit into 120 Volt grounded power supply and test operation NOTE When switch is in the AUTO...

Page 16: ...ff On Blue Blue Thermostat Switch N O Green White Green White On 110 115 V A C Blower Motor Black Off 1 2 3 Auto Figure 18 Installing Switch Plate to Valve Cover Shield Valve Cover Shield Switch Plate...

Page 17: ...e 19 4 Plug power cord to the outlet receptacle not provided as shown in Figure 20 Wind the extra power cord and tie with plastic wire strap see Figure 20 Set the power cord bundle between the burner...

Page 18: ...O GAS SUPPLY WARNING Thisappliancerequiresa 45 maleflarefitting5 8 18UNF Unified National Fine Thread inlet connection and the flexible gas line provided WARNING A qualified service person must connec...

Page 19: ...e controls If sediment trap is not installed or is installed wrong fireplace may not run properly Figure 24 Attaching Flexible Gas Line to Equipment Shutoff Valve Flexible Gas Line from Fireplace Gas...

Page 20: ...all leaks at once CAUTION Make sure external regulator has been installed between propane LPsupplyandappliance See guidelines under Connecting to Gas Supply Page 18 CHECKING GAS CONNECTIONS Test Press...

Page 21: ...ed Wire 3 Route 25 ft wire to a convenient location to mount your thermostat no outside wall IM PORTANT Wire may be shortened but must not be lengthened Thermostat should be mounted 54 above the floor...

Page 22: ...n should be done by a qualified installer familiar with low voltage wiring procedures WARNING Do not connect the switch to a power source Electrical shock and or fire hazard will occur WARNING Do not...

Page 23: ...supplier Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the applia...

Page 24: ...pilot with match To light pilot with match see Manual Lighting Procedure Page 25 8 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If control kno...

Page 25: ...may run for several minutes before blower turns on After heater modulates to pilot position blower will continue to run The blower will shut off after firebox temperature decreases MANUAL LIGHTING PRO...

Page 26: ...have a slight curve but flame should be blue and have no yellow or orange color Figure 38 Correct Pilot Flame Pattern Propane LP Shown Pilot Burner Thermocouple Figure 39 Incorrect Pilot Flame Pattern...

Page 27: ...yearly by a qualified serviceperson Heatermayneedmore frequentcleaningduetoexcessivelint from carpeting bedding material pet hair etc BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE The primary air in...

Page 28: ...or placement instructions Replace log set if broken or chipped dime sized or larger CABINET Air Passageways Use a vacuum cleaner or pressurized air to clean Exterior Use a soft cloth dampened with a m...

Page 29: ...f pinched by any metal or tubing Keep igniter cable dry 3 Replace igniter cable 4 Replace piezo igniter 5 Replace pilot assembly 6 Replace pilot assembly When igniter button is pressed there is spark...

Page 30: ...ean ing and Maintenance Page 27 or replace ODS pilot as sembly 6 Hand tighten until snug then tighten 1 4 turn more 7 Replace pilot assembly 8 Replace control valve Burner does not light after ODS pil...

Page 31: ...eplace blocked 4 Dirty or partially clogged burner orifice 1 Turn control knob to LO posi tion and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by loc...

Page 32: ...exces sive contact qualified service person Fireplace produces unwanted odors 1 Fireplace burning vapors from paint hair spray glues clean ers chemicals newcarpet etc See IMPORTANT statement above 2 L...

Page 33: ...ignition appliance will not produce specified heat propane LP gas supply may be low You may feel your gas pressure is too low If so contactyourlocalpropane LPornaturalgassupplier TECHNICAL SERVICE You...

Page 34: ...t No F2236 Model RCKIT4001 For all models Allows appliance to be operated in a manually controlled mode RECEIVER AND HAND HELD THERMOSTATIC ON OFF REMOTE CONTROL KIT TRC Cat No F1078 Model TRC For all...

Page 35: ...32 13 41 21 5 26 19 18 15 27 1 27 2 43 3 43 29 16 18 3 17 42 36 4 4 44 43 Cat No Model Description F1217 VCM3026ZMN 26 Millivolt NG F1218 VCM3026ZMP 26 Millivolt LP WARNING Failure to position the pa...

Page 36: ...1 J3837 Gas Valve LP 1 23 J3757 Baffle 1 24 J3725 Flexible Connector 1 25 J3868 Control Shield 1 26 J3802 Screen Assembly 1 27 J4008 Log Set Assembly Kit 1 28 J3869 Right Hinge 1 29 J3870 Left Hinge 1...

Page 37: ...tural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c...

Page 38: ...ts Consult your local distributor for fireplace code information Printed in U S A 2014 Innovative Hearth Products P N 126872 01 Rev C 12 2019 SuperiorFireplaces us com Record the following important i...

Reviews: