Page | 48
Hybrid Inverter | Installer Manual
Therefore, if a communication error occurs:
1. Check that your data cable is the correct type.
2. Check that the data cable is plugged into the correct sockets. Usually, RS485 is employed,
but some battery manufacturers use others..
It is important to refer to the manuals that manufacturers produce for their batteries. That way,
the chance of errors occurring during installation are greatly reduced. Below there is a list of
batteries that has been examined, tested, and approved by Sunsynk.
With some types of lithium battery, the BMS cannot be controlled by the Sunsynk
inverter. In this case, treat the battery as a lead-acid type and set the charging and
discharging protocol following the battery manufacturer specification.
Brand
Model
48V
Storage
Inverter
RS485
or CAN
Inverter
Setup
Notes
PYLON
US2000B
CAN
0
RS485
12
US3000
CAN
0
RS485
12
US2000C
CAN
0
RS485
12
US3000C
CAN
0
RS485
12
UP5000
CAN
0
RS485
12
US5000
CAN
0
RS485
12
Force L1
CAN
0
RS485
12
Force L2
CAN
0
RS485
12
DYNESS
B4850
CAN
0
POWERBOXF
0
SolarMD
SS4074
CAN
0
To be used with V2 Log-
ger http://solarmd.co.za/
inverter-compatibility-so-
larmd/ sunsynk-and-so-
lar-md/
SS4037
0
SS202
0
SHOTO
SDC10-Box 5
CAN
0
Summary of Contents for SUN-25K-SG01HP3-EU-BM2
Page 19: ...Page 19 Hybrid Inverter Installer Manual 4 4 1 Function Ports Definition ...
Page 26: ...Page 26 Hybrid Inverter Installer Manual ...
Page 27: ...Page 27 Hybrid Inverter Installer Manual ...
Page 29: ...Page 29 Hybrid Inverter Installer Manual 4 10 Wiring System for Inverter ...
Page 30: ...Page 30 Hybrid Inverter Installer Manual 4 11 Wiring Diagram ...
Page 31: ...Page 31 Hybrid Inverter Installer Manual ...
Page 32: ...Page 32 Hybrid Inverter Installer Manual 4 12 Typical Application Diagram of Diesel Generator ...