Page | 51
Hybrid Inverter | Installer Manual
When communications between battery and inverter does not exist, do not over-
charge your battery bank (current or voltage). Many lithium batteries are limited to
100A, some are lower and some are higher. Ensure that voltage and current speci-
fications provided by the battery manufacturer are followed.
If you are using lead acid batteries then follow the equation of C x 0.25 which means
that the maximum charge or discharge you can apply to a battery is a quarter of the
AH rating of the overall battery array. Eg.; A 200Ah battery array composed of 4 x
200Ah batteries in series has a maximum discharge of only 50Ah (200 x 0.25 = 50)
Also, ensure the cable is thick enough to support the current and the fuses con-
nected are of the correct rating as per the recommendations of battery manufac-
turers.
Brand
Model
48V
Storage
Inverter
RS485
or CAN
Inverter
Setup
Notes
BSL
B-LFP51.2V 100Ah
CAN
0
Float voltage 54.5V
Absorption V 55.00V
Disable equalisation 0 Days
Shutdown 20%
Low Batt 35%
Restart 50%
B-FLP51.2V 125Ah
B-LFP48-130E 51.2V
130Ah
B-LFP48-160E 51.2V
160Ah
B-LFP51.2V 200Ah
Powerwall
Enersol
lithium 48-100
CAN
0
BMS cable – straight RJ45
cable ( no need to change
pin outs on cable)
Dip Switch settings is 1000 (
for single battery
)
Summary of Contents for SUN-25K-SG01HP3-EU-BM2
Page 19: ...Page 19 Hybrid Inverter Installer Manual 4 4 1 Function Ports Definition ...
Page 26: ...Page 26 Hybrid Inverter Installer Manual ...
Page 27: ...Page 27 Hybrid Inverter Installer Manual ...
Page 29: ...Page 29 Hybrid Inverter Installer Manual 4 10 Wiring System for Inverter ...
Page 30: ...Page 30 Hybrid Inverter Installer Manual 4 11 Wiring Diagram ...
Page 31: ...Page 31 Hybrid Inverter Installer Manual ...
Page 32: ...Page 32 Hybrid Inverter Installer Manual 4 12 Typical Application Diagram of Diesel Generator ...