ECCO SG04LP1 | User Manual
61
Error Code
Description
Solutions
F24
DC insulation im-
pedance failure
PV isolation resistance is too low
1.Check if the connection of PV panels and inverter are firmly con
-
nected.
2.Check if the earth bond cable on inverters is connected to the
ground.
F26
The bus bar is un-
balanced
1.Please wait 5 minutes to see if it returns to normal.
2. Fully reset the inverter.
F35
No at: grid
Grid voltage fault
1.Check if the voltage is in the range of standard voltage in specifica
-
tion this can be adjusted via the grid set up page.
2.Check if grid cables are correctly connected.
F42
AC line low voltage
Grid voltage fault
1.Check if the voltage is in the range of standard voltage in specifica
-
tion this can be adjusted via the grid set up page.
2.Check if grid cables are correctly connected.
F47
AC over frequency
Grid frequency out of range
1.Check if the frequency is in the range of specification
2.You may need to adjust the frequency on the grid set up page.
F48
DC bus bar voltage
is too low
Battery low voltage
1. Check if the battery voltage is too low.
2. If the battery voltage is too low use the PV or grid to charge the
battery.
3. Check the battery BMS
Important:
Especially with Lithium batteries, ensure that the bat-
teries Max. discharge current or power specification is the same or
higher than the inverter specification.
F64
Heat sink high-tem-
perature failure
Heat Sink temp is too high
1.Check if the working environment temperature is too high.
2.Turn off the inverter for 30 minutes and restart.
Fault
Information
Instruction
Fault
Information
Structure
F01
DC_Inversed_Failure
F33
AC_OverCurr_Fault
F02
DC_Insulation_Failure
F34
AC_Overload_Fault
F03
GFDI_Failure
F35
AC_NoUtility_Fault
F04
GFDI_Ground_Failure
F36
AC_GridPhaseSeque_Fault
F05
EEPROM_Read_Failure
F37
AC_Volt_Unbalance_Fault
F06
EEPROM_Write_Failure
F38
AC_Curr_Unbalance_Fault
F07
GFDI_Fuse_Failure
F39
INT_AC_OverCurr_Fault
Summary of Contents for ECCO SUN-3.6K-SG05LP1-EU
Page 9: ...ECCO SG04LP1 User Manual 9 2 1 Product Size ...
Page 17: ...ECCO SG04LP1 User Manual 17 4 5 Function Port Definition ...
Page 21: ...ECCO SG04LP1 User Manual 21 ...
Page 23: ...ECCO SG04LP1 User Manual 23 4 9 1 Recommended AC Surge Protector ...
Page 26: ...ECCO SG04LP1 User Manual 26 4 12 Meter Connection 4 12 1 System Connection for the CHNT Meter ...
Page 27: ...ECCO SG04LP1 User Manual 27 4 13 Wiring System for Inverter ...
Page 30: ...ECCO SG04LP1 User Manual 30 4 16 Single Phase Parallel Connection Diagram 03 02 01 ...
Page 31: ...ECCO SG04LP1 User Manual 31 4 17 Three Phase Parallel Inverter 03 02 01 ...
Page 32: ...ECCO SG04LP1 User Manual 32 4 18 Typical Application Diagram of Diesel Generator ...
Page 63: ...ECCO SG04LP1 User Manual 63 6 OPERATING MODES 6 1 Mode I Basic 6 2 Mode II With Generator ...
Page 64: ...ECCO SG04LP1 User Manual 64 6 3 Mode III With Smart Load 6 4 Mode IV AC Couple ...
Page 65: ...ECCO SG04LP1 User Manual 65 ...
Page 71: ...Ltd wered by Po ...