System Manual
3 Product Description
15
3.4.2
Cable Entry Design
For convenient cable connection in the field, all cables among the MV Station internal
devices are connected before delivery.
All cables between the MV Station and the external are routed through the bottom of the
MV Station. All cables come into or out of the MV Station should be protected properly, for
example, cable pipe to prevent damage by rodents. After cable connection, all cable entries
except for cable glands should be sealed by fireproof mud or other appropriate materials.
The MV Station bottom cable entries are shown below.
Hole-1
Hole-2
Hole-3
Hole-4
Fig. 3-3
Cable entries of the MV Station
Function of each opening is shown below:
Item
Name
Description
Hole-1
DC cable inlet
DC cables connect to the MV Station through these two
holes.
Hole-2
Reserved hole
-
Hole-3
Communication
cable inlet
Communication and power supply cables connecting the
MV Station go in/out through this hole
Hole-4
AC cable outlet
AC cables of transformer high voltage side connect to the
downstream public grid through this hole.
Dimensions of the holes
Unit: mm
370
678
370
678
876
311
100
165
140
140