User Manual
87
Fig. 9-18
Protection parameter
For convenient protection parameter setting, the protection parameters are
preset for certain countries. After country setting, select the protection stage as
single or multiple and then set the corresponding protection parameter.
Tab. 9-9
Single-stage Protection Parameters Explanation
Parameter
Default
Range
AC under-voltage single-stage protection value
528.0V
60V-600V
AC over-voltage single-stage protection value
660.0V
600 -840V
AC under-frequency single-stage protection
value
58.50Hz
50Hz -59.88Hz
AC over-frequency single-stage protection
value
60.50Hz
60.12Hz -65Hz
Tab. 9-10
Multi-stage Protection Parameters Explanation
Parameter
Default
Range
AC under-voltage level 1 protection value
528.0V
60V-600V
AC over-voltage level 1 protection value
660.0V
600 -840V
AC under-frequency level 1 protection value
58.50Hz
53Hz -59.88Hz
AC over-frequency level 1 protection value
60.50Hz
60.12Hz -65Hz
AC under-voltage level 1 protection time
21.00s
0.05s-600s
AC over-voltage level 1 protection time
13.00s
0.05s-600s
AC under-frequency level 1 protection time
300.00s
0.05s-600s
AC over-frequency level 1 protection time
300.00s
0.05s-600s
AC under-voltage level 2 protection value
420V
60V-600V