User Manual
33
Bottom view
8
9
10
11
13
12
Fig. 5-1
Cable connection area
*Pictures are indicative only. Please in kind prevail.
No.
Name
Description
1
DC switch
Protective components to safely disconnect
DC side current.
2
Configuration circuit board
Communication cable connection and
configuration
3
DC crimping terminal
DC input cable access
4
AC crimping terminal
AC output cable access
5
AC PE terminal
AC PE cable access, M10X30 fastening
screws
6
AC switch
Serviced as an automatic overcurrent
device
7
DC PE terminal
DC PE cable access, M6
×
16 (right) or
M10X30 (left)fastening screws
8
Waterproof air valve
-
9
Communication
cable
gland
For Communication cable (Parallel CAN
communication
cable,
carrier
synchronization
cable,
EMS200
communication cable) connection.
10*
DC cable gland
For DC cable connection
Knockout diameter for DC cable is 75.8mm.
(The proper range of DC cable external
diameter is 20~26mm)
11*
AC cable gland
For AC cable connection
Knockout diameter for AC cable is 75.8mm.
(The proper range of AC cable external
diameter is 38~56mm)
12
AC
cable
gland
for
connecting Tracker control
cabinet
Reseved