* Please follow the rules below to set parameters:
AC under-voltage level 1 protection value
≥
AC under-voltage level 2
protection value
≥
AC under-voltage level 3 protection value;
AC over-voltage level 1 protection value
≤
AC over-voltage level 2 protection
value
≤
AC over-voltage level 3 protection value;
AC under-frequency level 1 protection value
≥
AC under-frequency level 2
protection value
≥
AC under-frequency level 3 protection value;
AC over-frequency level 1 protection value
≤
AC over-frequency level 2
protection value
≤
AC over-frequency level 3 protection value;
AC under-voltage level 1 protection time
≥
AC under-voltage level 2
protection time
≥
AC under-voltage level 3 protection time;
AC over-voltage level 1 protection time
≥
AC over-voltage level 2 protection
time
≥
AC over-voltage level 3 protection time;
AC under-frequency level 1 protection time
≥
AC under-frequency level 2
protection time
≥
AC under-frequency level 3 protection time;
AC over-frequency level 1 protection time
≥
AC over-frequency level 2
protection time
≥
AC over-frequency level 3 protection time;
AC under-voltage recovery value
≥
AC under-voltage level 1 protection value
+ 3V;
AC over-voltage recovery value
≤
AC over-voltage level 1 protection value -
3V;
AC under-frequency recovery value
≥
AC under-frequency level 1 protection
value + 0.01Hz;
AC over-frequency recovery value
≤
AC over-frequency level 1 protection
value - 0.01Hz.
The range and default value in the table above is indicative only.
The protection parameter varies in different countries. Please refer to
the standards of each country for details.