User Manual
88
Parameter
Default
Range
AC over-voltage level 2 protection value
720.0V
600 -840V
AC under-frequency level 2 protection value
57Hz
53Hz -59.88Hz
AC over-frequency level 2 protection value
62Hz
60.12Hz -65Hz
AC under-voltage level 2 protection time
11.00s
0.05s-600s
AC over-voltage level 2 protection time
0.16s
0.05s-600s
AC under-frequency level 2 protection time
0.16s
0.05s-600s
AC over-frequency level 2 protection time
0.16s
0.05s-600s
AC under-voltage level 3 protection value
300V
60V-600V
AC over-voltage level 3 protection value
720V
600 -840V
AC under-frequency level 3 protection value
57Hz
53Hz -59.88Hz
AC over-frequency level 3 protection value
62Hz
60.12Hz -65Hz
AC under-voltage level 3 protection time
1.5s
0.05s-600s
AC over-voltage level 3 protection time
0.16s
0.05s-600s
AC under-frequency level 3 protection time
0.16s
0.05s-600s
AC over-frequency level 3 protection time
0.16s
0.05s-600s
AC under-voltage level 4 protection value
300V
60V-600V
AC over-voltage level 4 protection value
720V
600 -840V
AC under-frequency level 4 protection value
57Hz
53Hz -59.88Hz
AC over-frequency level 4 protection value
62Hz
60.12Hz -65Hz
AC under-voltage level 4 protection time
1.5s
0.05s-600s
AC over-voltage level 4 protection time
0.16s
0.05s-600s
AC under-frequency level 4 protection time
0.16s
0.05s-600s
AC over-frequency level 4 protection time
0.16s
0.05s-600s
AC under-voltage level 5 protection value
300V
60V-600V
AC over-voltage level 5 protection value
720V
600 -840V
AC under-frequency level 5 protection value
57Hz
53Hz -59.88Hz
AC over-frequency level 5 protection value
62Hz
60.12Hz -65Hz
AC under-voltage level 5 protection time
1.5s
0.05s-600s
AC over-voltage level 5 protection time
0.16s
0.05s-600s
AC under-frequency level 5 protection time
0.16s
0.05s-600s
AC over-frequency level 5 protection time
0.16s
0.05s-600s
Proceed to set the protection recovery value after setting the single-stage/multi-
stage protection stage.
Tab. 9-11
Description of protection recovery parameters
Parameter
Explanation
Default
Range
Vmax-
recover
Max. protection recovery voltage
635.0V
600V - 840V
Vmin-recover
Min. protection recovery voltage
531.0V
60 -600V
Fmax-
recover
Max.
protection
recovery
frequency
60.49Hz
60.11Hz
-
64.99Hz
Fmin-recover
Min.
protection
recovery
frequency
58.30Hz
50.01Hz
-
59.89Hz
Summary of Contents for SG125HV-30
Page 1: ...SG125HV 30 UEN Ver11 202003 Version 1 1 User Manual SG125HV 30 PV Grid connected Inverter...
Page 2: ......
Page 10: ......