8 Troubleshooting and Maintenance
User Manual
64
Fault
code
Description
Check method
021-022
Device anomaly
Wait for the inverter to return to normal.
Disconnect the AC and DC switches, and
reconnect the AC and DC switches 15
minutes later to restart the inverter.
If the fault still exists, contact Sungrow
Service.
024-025
030-034
Device anomaly
Wait for the inverter to return to normal.
Disconnect the AC and DC switches, and
reconnect the AC and DC switches 15
minutes later to restart the inverter.
If the fault still exists, contact Sungrow
Service.
036
Temperature
anomaly,
The temperature of
the power module
or the interior of the
inverter
is
excessively
high
and out of the safe
range.
1. Check whether the inverter is directly
exposed to sunlight. If so, take some shading
measures.
2. Check and clean the air ducts.
3. Check whether there is 070 (fan anomaly)
alarm via the APP or the LCD. If so, replace
the fans.
037
Temperature
anomaly,
The temperature of
the power module
or the interior of the
inverter
is
excessively
high
and out of the safe
range.
1. Check whether the inverter is directly
exposed to sunlight. If so, take some shading
measures.
2. Check and clean the air ducts.
3. Check whether there is 070 (fan anomaly)
alarm via the APP or the LCD. If so, replace
the fans.
038
Device anomaly
Wait for the inverter to return to normal.
Disconnect the AC and DC switches, and
reconnect the AC and DC switches 15
minutes later to restart the inverter.
If the fault still exists, contact Sungrow
Service.