10 Operation of LCD Display Panel
User Manual
72
10.10.2 Reactive Power Regulation
The inverter provides reactive power regulation function. Use the “
Q-Var switch
”
parameter to activate this function and select proper regulation mode.
Regulation Mode
Explanation
Pf
The reactive power can be regulated by the parameter
PF
(Power Factor)
.
Qt
The reactive power can be regulated by the parameter
Q-Var
limits
(in %).
Off
The
PF
is limited to +1.000, and the “
Q-Var limits”
is limited to
0.0%.
Q(P)
The PF changes with the output power of the inverter.
Q(U)
The reactive power changes with the grid voltage.
“
Pf
” Mode
The reactive power can be regulated by the parameter
PF
on the Run-param screen.
“
Qt
” Mode
The reactive power can be regulated by the parameter
Q-Var limits (in %)
on the
Run-param screen.
“
Off
” Mode
The
PF
is limited to +1.000, and the
Q-Var limit
is limited to 0.0%.
“
Q(P)
” Mode(when the country selection is not “IT”)
The PF changes with the inverter output power.
If the country selection is not “IT” (Italy), after
selecting Q(P) Mode,
Press
j
to enter the
Run-param-Q(P) sub-menu.
For each item setting,
Press
h
to move cursor right
and
Press
j
to set the appropriate value. Confirm
settings by Press
ENTER
.
Tab. 10-5
“
Q(P)
” Mode Parameters Explanation
Parameter
Explanation
Default
Range
Upper PF Cap
Power factor of point P1 in the Q(P) mode
curve
1 0.9…1
Lower
Power*
Output power of point P1 in the Q(P)
mode curve (in %)
50% 0%...50%
Lower PF Ind
Power factor of point P2 in the Q(P) mode
curve
0.9 0.9…1
Summary of Contents for SG10KTL
Page 2: ......