6 Electrical Connection
37
Parallel Mode
In parallel mode, the PV inputs can be connected in parallel, with sharing the same
MPPT, as the following diagram shown. One pair of DC terminals in DC1 input and
DC2 input must be short-circuited.
To make sure the maximum DC power can be utilized; All PV strings
connected to inverter should have a homogenous structure, including
the same type, the same number, identical tilt and identical orientation.
Prior to connecting inverter to PV inputs, the following specifications should be met:
Type
Total DC Power
Limit for Inverter
Open-circuit
Voltage Limit for
Each Input
Short-circuit
Current Limit for
Total Input
SG10KTL
10800W
1000V
50A
SG12KTL
12800W
1000V
50A
SG15KTL
15800W
1000V
50A
SG20KTL
21000W
1000V
50A
There is a risk of inverter damage! The following requirements should be
met; otherwise they will lead to loss of any or all warranty rights.
y
Make sure that the maximum short circuit current of each DC input is less
than the inverter allowable limit.
y
Make sure that the maximum open voltage of each string is less than
1000V. Voltage over 1000V can damage the inverter.