TABLE 12–7
Message
Type
Description
TEMPERATURE WARNING: X
degrees celsius at location
Y.
Warning
Indicates that the temperature
measured at location Y has
exceeded the warning threshold
and if it continues to overheat the
system will shutdown.
If the value of location Y is a
sensor on a CPU, (CP0 or CP1) the
temperature (identified by the
value X) has exceeded 60 degrees
C.
If the value of location Y is a sensor
on the PDB (power distribution
board), SCSI backplane, MB0 or
MB1 (main logic board), the
ambient temperature (identified by
the value X) has exceeded 53
degrees C.
TEMPERATURE CRITICAL:
X
degrees celsius at location Y.
Warning
Indicates that the temperature
measured at location Y has
exceeded a critical threshold. After
this warning message, the system
automatically shuts down.
If the value of location Y is a
sensor on a CPU, (CP0 or CP1) the
temperature (identified by the
value X) has exceeded 65 degrees
C.
If the value of location Y is a sensor
on the PDB (power distribution
board), SCSI backplane, MB0 or
MB1 (main logic board), the
ambient temperature (identified by
the value X) has exceeded 58
degrees C.
Power Supply X NOT okay.
Warning
Indicates that there is something
wrong with the DC output of the
supply. The system may shut down
abruptly if the redundant power
supply fails. The value X identifies
the power supply, PS0 is the lower
power supply; PS1 is the upper
power supply.
274
Sun Enterprise 250 Server Owner’s Guide
♦
Revision A, June 1998
Summary of Contents for Enterprise 250
Page 2: ...USA 650 960 1300 fax 650 969 9131 ...
Page 3: ...Sun Enterprise 250 Server Owner s Guide Part No 805 3389 11 Revision A June 1998 ...
Page 44: ...10 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 45: ...CHAPTER 2 Photographic Tour of System System View 11 ...
Page 48: ...Figure 2 2 14 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 52: ...Figure 2 4 18 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 69: ...Power Distribution Board Photographic Tour of System 35 ...
Page 88: ...54 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 102: ...68 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 160: ...126 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 212: ...178 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 226: ...Figure 9 8 192 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 228: ...194 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 266: ...232 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 310: ...276 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 324: ...290 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 330: ...296 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 346: ...312 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...
Page 356: ...TABLE D 6 continued 322 Sun Enterprise 250 Server Owner s Guide Revision A June 1998 ...