SECTION 4
TSR32 USER MANUAL R00
35
4.7
ELECTRICAL PREPARATION
Interior electrical wiring is installed at the factory.
Required customer wiring should be done by a
qualified electrician in compliance with OSHA,
National Electric Code and/or any applicable local
electrical codes. Customer to supply power via cam-
lock located on end of enclosures. An electrical
check should be made to ensure that the first start-up
will be successful. The compressor and drive should
be properly grounded/earthed in accordance with
applicable codes, regulations, and requirements.
Feeder cables should be sized by the customer/
electrical contractor to ensure that the circuit is
balanced and not overloaded by other electrical
equipment. The length of wiring from a suitable
electrical power source is critical because voltage
drops can adversely effect the performance of the
compressor. Refer to
Table 4-2:Motor Wiring Basic
Data
.
Parallel feeder cable connections to incoming
terminal cam-locks L1-L2-L3 should be tight and
clean. These are located on end of package. Behind
the access door located above the cam-loks is the
package circuit breaker disconnect, supplied for
additional safety.
The applied voltage must conform to the motor and
compressor data plate ratings.
1. Check incoming voltage. The incoming
rating/specifications.
2. Check motor starting device and overload
heater sizes.
3. Check all electrical connections
for
tightness.
Table 4-2: Motor Wiring Basic Data
480 V 40 C
HP (I low)
Current I
low OL
Phase Wire
MCM
GND
Conductor
MAX 300 HP
385
2x300
300MCM
WARNING
Energized internal components are a poten-
tially FATAL SHOCK HAZARD. Disconnect
all power before performing any work on the
Summary of Contents for TSR20
Page 10: ...NOTES 10...
Page 17: ...SECTION 2 TSR32 USER MANUAL R00 17...
Page 24: ...NOTES 24...
Page 27: ...NOTES 27...
Page 28: ...TSR32 USER MANUAL R00 SECTION 3 28 02250175 423 R01...
Page 29: ...SECTION 3 TSR32 USER MANUAL R00 29 02250177 017 R01...
Page 30: ...TSR32 USER MANUAL R00 SECTION 3 30 Figure 3 4 Wiring 02250177 397 R00...
Page 31: ...SECTION 3 TSR32 USER MANUAL R00 31 02250177 398 R00...
Page 32: ...NOTES 32...
Page 46: ...NOTES 46...
Page 47: ...NOTES 47...