background image

TSR32 USER MANUAL R00

SECTION 2

16

System

 consist of 

variable speed drive

 and 

spiral

valve

.  The  functional  description  of  the  control

system  is described  below  in  five  distinct  phases of

operation.  The  following  description  text  applies  to

TSR-20  variable  speed  drive  compressors  with

The  compressor  can  be

operated  at  a  setpoint  pressure  from  100  to  175

psig  (4.1  to  12.1  bar)  along  with  a  horsepower

range  from  200  to  300  HP.  The  Supervisor

range  based  on  the  selected  pressure  and

horsepower. 

For  explanatory  purposes,  this

description  will  apply  to  a  compressor  with  an

operating  pressure  of  100  psig  (6.9  bar).  A

compressor  with  any  other  pressure  range  would

operate  in  the  same  manner  except  stated

pressures.

PSIG (0 TO 3.4 BAR)

START

)

button is depressed, the VSD ramps the motor to full

speed and the sump pressure will quickly rise from 0

to 50 psig (0-3.4 bar). During this period, the solenoid

valve is closed,  the  inlet  valve is  fully open  and  the

air-end delivers full capacity to the sump tank.  The

rising  compressor  air  pressure  is  isolated  from  the

service  line  in  this  phase  by  the  minimum  pressure

valve set at approximately 50 psig (3.4 bar).

FULL LOAD MODE- 50 TO 100 PSIG (3.4 TO 6.9 BAR) 

When  the  compressed  air  pressure  rises  over  50

psig  (3.4  bar)  the  minimum    pressure  valve  is

opened  allowing  compressed  air  to  flow  into  the

service line. From  this point on the line pressure is

which controls the variable speed drive. The solenoid

valve  remains  closed  with  the  inlet  valve  fully  open

running at 100 psig (6.9 bar) or below.

VARIABLE SPEED DRIVE PART LOAD CONTROL 

If less than rated capacity of compressed air is being

used,  the  service  line  pressure  will    rise  above  100

psig  (6.9  bar).    Consequently,  the  Variable  Speed

Drive  will  begin  to  decelerate  the  motor,  thereby

reducing the output capacity to match demand.  The

drive  will  continuously  adjust  the  motor  speed

(accelerate or decelerate) to maintain a line pressure

of    100  psig  (6.9  bar).    In  this  mode  the  VSD  will

operate  within  the  appropriate  frequency  range

determined by the Su

MODULATING MODE WITH SPIRAL VALVE: 

As  demand  decreases,  the  variable  speed  drive

reduces motor speed to maintain the set point pres-

sure.    When  the  speed  approaches  the  minimum

setting, a solenoid valve opens feeding air pressure

to the spiral valve actuator.  This in turn expands the

diaphragm  and engages the  pinion  mounted  on  the

spiral  valve  shaft  assembly,  resulting  in  a  rotary

motion  and  full  opening  of  the  spiral  valve,  effec-

tively reducing  the  rotor  length by  50%.   Excess  air

will be returned back internally to the suction side of

the  compressor  unit.    In  this  mode,  the  VSD  will

modulate the motor speed within a specified range to

maintain the set point pressure as follows: 

Increasing demand condition: 

If  demand  increases,  the  VSD  increases  the  motor

speed until the set point pressure is achieved.  If set

point  pressure  is  not  achieved  while  at  maximum

speed,  the  controller  will  close  the  spiral  valve,

thereby 

eliminating 

internal 

air 

bypass.

Consequently, the VSD will regulate the motor speed

to achieve the set point pressure. 

Decreasing demand condition: 

While the spiral valve is open, if demand continues to

decrease the VSD will reduce the motor speed until

the  set  point  pressure  is  achieved.    This  action  will

continue until the minimum speed is reached. When

the  system  pressure  reaches  106  psig  (7.3  bar),  or

alternatively  set  unload  pressure,  the  compressor

unloads, or turns off. 

UNLOAD MODE- IN EXCESS OF 106 PSIG (7.3 BAR) 

When  a  relatively  small  amount  or  no  air  is  being

used,  the  service  line  pressure  continues  to  rise.

When it  exceeds 106 psig (7.3 bar), or alternatively

control  system  de-energizes  the  solenoid  valve

allowing sump air pressure to be supplied directly to

close  the  inlet  valve.  Simultaneously,  the  solenoid

valve  sends  a  pneumatic  signal  to  the  blow  down

valve.  The  blow-  down  valve  opens  to  the

atmosphere,  reducing  sump  pressure.  The  check

valve  in  the  air  service  line  prevents  line  pressure

from returning to the sump.  The compressor will shut

down  after  the  unload  time  setting  expires  if

programmed (the default setting is zero [0] seconds

for an immediate shutdown upon unload). 

When  the  line  pressure  drops  to  the  low  setting

pressure  of  100  psig  (6.9  bar)  The  Supervisor

noid  valve  which  closes  the  blow  down  valve.    The

re-energized  solenoid  valve  prevents  line  pressure

from  reaching  the  inlet  control  valve,  thereby  allow-

ing it to fully open. 

AUTOMATIC OPERATION

For  VSD  applications,  th

allows  the  compressor  to  shutdown  when  no  com-

pressed air requirement is present and restarts when

compressed  air  is  needed.  Restart  will  only  take

place when sump pressure is below 5 psig.

Summary of Contents for TSR20

Page 1: ...Y NOTICE PART NUMBER KEEP FOR FUTURE REFERENCE USER MANUAL SULLAIR CORPORATION The information in this manual is current as of its publication date and applies to compressor serial number and all subs...

Page 2: ...City Indiana Instruction includes training on the function and installation of Sullair service parts troubleshooting common faults and malfunctions and actual equipment operation These seminars are r...

Page 3: ...ING 9 1 10 ENTRAPMENT 11 2 1 INTRODUCTION 11 2 2 COMPRESSOR COMPONENT DESCRIPTION 15 2 3 COMPRESSOR COOLING AND AL DESCRIPTION 15 2 4 COMPRESSOR DISCHARGE SYST 15 2 5 VSD CONTROL SYSTEM 18 2 6 FIXED S...

Page 4: ...4 4 6 FLUID LEVEL CHECK 35 4 7 ELECTRICAL PREPARATION 36 4 8 MOTOR ROTATION DIRECTION CHECK 37 5 1 ROUTINE OPERATION SETUP 39 6 1 GENERAL 39 6 2 MAINTENANCE AFTER INITIAL 50 HOURS OF OPERATION 39 6 3...

Page 5: ...rein are applicable to most compressors and the concepts behind these statements are generally applicable to all compressors 1 2 PERSONAL PROTECTIVE EQUIPMENT A Prior to installing or operating the co...

Page 6: ...including air line anti icer system antifreeze compound or fluid film to accumulate on under or around acoustical mate rial or on any external surfaces of the air com pressor Wipe down using an aqueo...

Page 7: ...codes or regula tions B DO NOT use air line anti icer systems in air lines supplying respirators or other breathing air utili zation equipment and DO NOT discharge air from these systems into unventi...

Page 8: ...otating machinery and prior to handling any ungrounded conductors 1 9 LIFTING A If the compressor is provided with a lifting bail then lift by the bail provided If no bail is provided then lift by sli...

Page 9: ...a cles at floor level and transport and corner at minimum practical speeds N Make sure pallet mounted compressors are firmly bolted or otherwise secured to the pallet prior to attempting to forklift o...

Page 10: ...NOTES 10...

Page 11: ...directly with the air as the rotors turn which compresses the air The fluid flow has three basic functions 1 As a coolant it controls the air temperature rise normally associated with the heat of comp...

Page 12: ...TSR32 USER MANUAL R00 SECTION 2 12 Figure 2 1 Sullair TSR 32 Rotary Screw Air Compressor Air Cooled VSD...

Page 13: ...SECTION 2 TSR32 USER MANUAL R00 13 Figure 2 2 Sullair TSR 32 Rotary Screw Air Compressor Air Cooled Fixed Speed...

Page 14: ...TO FLUID COOLER CC FROM FLUID COOLER DD TO UNIT INJECTION BLOCK EE TO AFTERCOOLER FF FROM AFTERCOOLER GG AIR SUPPLY OUTLET HH MOISTURE DRAIN OUTLET 1 FLUID FILTER 2 FLUID STOP VALVE 3 MINIMUM PRESSUR...

Page 15: ...amount of fluid remaining in the compressed air collects on the surface of the separator elements as the air flows through the separators Two return lines or scavenge tube lead from the bottom of the...

Page 16: ...solenoid valve opens feeding air pressure to the spiral valve actuator This in turn expands the diaphragm and engages the pinion mounted on the spiral valve shaft assembly resulting in a rotary motio...

Page 17: ...SECTION 2 TSR32 USER MANUAL R00 17...

Page 18: ...tor for the spiral valve gradually opens apply ing air pressure to the spiral valve actuator Air pressure at the actuator expands the diaphragm The rack in turn engages with the pinion mounted on the...

Page 19: ...be disabled in the Supervisor modulation is disabled the unload pressure must be reset to the rated load pressure of the machine For example an L model rated for 100 psig full load operation and 110 p...

Page 20: ...TSR32 USER MANUAL R00 SECTION 2 20 Figure 2 6 TSR 32 Piping and Instrumentation VSD 02250177 348 R01...

Page 21: ...ELEMENT SECONDARY SEPARATOR 22 250034 123 1 ELEMENT PRIMARY SEPARATOR 23 02250117 009 2 GAUGE PRESSURE PLEASE NOTE WHEN ORDERING PARTS INDICATE SERIAL NUMBER OF COMPRESSOR 28 02250097 611 2 GLASS FLUI...

Page 22: ...TSR32 USER MANUAL R00 SECTION 2 22 Figure 2 7 TSR 32 Piping and Instrumentation Fixed Speed 02250177 349 R01...

Page 23: ...4 129 1 ELEMENT SECONDARY SEPARATOR 22 250034 123 1 ELEMENT PRIMARY SEPARATOR 23 02250117 009 2 GAUGE PRESSURE PLEASE NOTE WHEN ORDERING PARTS INDICATE SERIAL NUMBER OF COMPRESSOR 28 02250097 611 2 GL...

Page 24: ...NOTES 24...

Page 25: ...0 MOTOR TEFC HZ VOLTAGE 460 60 DRIVE AMP RATING 385A WEIGHT lbs 19 900 LENGTH in 220 WIDTH in 84 HEIGHT in 104 COMPRESSOR TSR 32 Type Rotary Screw Standard Operating Pressure 100 psig 7 bar 125 psig 9...

Page 26: ...oam ing filter plugging or orifice line obstruc tion CAUTION Do not mix different types of lubricants Mixing lubricants can cause malfunctions or compressor damage will void the com 1 Fluid Fill Port...

Page 27: ...NOTES 27...

Page 28: ...TSR32 USER MANUAL R00 SECTION 3 28 02250175 423 R01...

Page 29: ...SECTION 3 TSR32 USER MANUAL R00 29 02250177 017 R01...

Page 30: ...TSR32 USER MANUAL R00 SECTION 3 30 Figure 3 4 Wiring 02250177 397 R00...

Page 31: ...SECTION 3 TSR32 USER MANUAL R00 31 02250177 398 R00...

Page 32: ...NOTES 32...

Page 33: ...mponents faces absorb sound and reduce ambient noise levels Hard surfaces reflect noise and have little effect on ambient noise lev els 4 2 VENTILATION AND COOLING AIR COOLED COMPRESSORS clearance aro...

Page 34: ...iver Compressors have built in aftercoolers and are equipped with a condensate drain located next to the air outlet connection A drain line should be installed to remove the condensate which builds up...

Page 35: ...from a suitable electrical power source is critical because voltage drops can adversely effect the performance of the compressor Refer to Table 4 2 Motor Wiring Basic Data Parallel feeder cable connec...

Page 36: ...once quickly and in succession the START and STOP pads This action will bump start the motor When looking from the motor end opposite the compressor unit the shaft should turn clockwise If reverse ro...

Page 37: ...6 8 Troubleshooting Introduction on page 43 under EXCESSIVE COMPRESSOR FLUID CONSUMPTION for a probable cause and corrective action After a routine start observe the controller display for the proper...

Page 38: ...0XH 175 PSIG TSR32_300L 100 PSIG TSR32_300H 125 PSIG TSR32_300HH 150 PSIG TSR32_300XH 175 PSIG Cooling Air Press Trans 250PSI P1 Max Maximum discharge pressure KT Fluid No Water Switch No Oil Switch N...

Page 39: ...d Piping System 2 Replace the fluid filter element 6 4 FLUID MAINTENANCE Drain the receiver tank and change the compressor fluid using instructions shown in the Lubrication Guide 6 5 FILTER MAINTENANC...

Page 40: ...ELEMENT REPLACEMENT Element replacement is performed by reversing the removal instructions Make sure that the element is fully seated into the housing 6 7 SEPARATOR MAINTENANCE Replace the separator...

Page 41: ...ssor 11 Check the return line strainer before re start ing the compressor If needed either clean or replace the strainer FLUID RETURN SIGHT GLASS MAINTENANCE Refer to Figure 6 4 The fluid return sight...

Page 42: ...406480 or order repair kit 250031 271 Figure 6 4 Fluid Return Sight Glass 1 Tube Connectors 2 Filter Assembly I 3 Sight Glass Orifice Block 4 Secondary Element orifice 03 5 Primary Element orifice 09...

Page 43: ...ng element from the coupling jaws 5 Install the new element by wrapping it around the jaws engaging the cogs on the element into the jaws 6 Reinstall the outer sleeve and secure by tightening the two...

Page 44: ...ar for integrated coolers 50 psig 3 4 bar for remote coolers when maximum operating pressure is reached Repair if defective Open or shorted P1 P2 P3 or P4 sensor message replace sensor indicated Opera...

Page 45: ...place if necessary kit available Ruptured Sullicon control diaphragm Replace Plugged control line filter Clean or repair if necessary Excessive Fluid Consumption Clogged return line strainer or orific...

Page 46: ...NOTES 46...

Page 47: ...NOTES 47...

Page 48: ...sors LTD Princes Highway Hallam Victoria 3803 Australia Telephone 61 3 9703 8000 Fax 61 3 9703 8053 www championcompressors com au SULLAIR CORPORATION 3700 East Michigan Boulevard Michigan City Indian...

Reviews: