Section 5
29
EES USER MANUAL
SETTINGS AND OPERATION
5.1
SETTINGS AND OPERATION
REJECTED AND RECOVERED AIR
ACTUATOR
The rejected and recovered air actuators control
distribution of heated cooling air. Refer to Section 2
for more a more detailed functional description.
Actuators are installed and set at the factory. The
following information is for reference and
troubleshooting.
D
IRECTION
OF
R
OTATION
:
Indicated on actuator housing. Can be changed
depending on damper/actuator location, see
. Both rejected and recovered dampers shall be
set to normally closed.
M
ANUAL
P
OSITIONING
:
In case of component failure or service needs, the
actuators can by manually operated and locked in
place. Using a 3mm hex, rotate the actuator in the
direction indicated on the case. When at desired
location, lock in place using a screwdriver on the
locking pin located on the lower portion of the
housing (
INCOMING AND BYPASS AIR
ACTUATORS
The incoming and bypass air actuators modulate to
maintain the desired mixed air temperature. Refer to
Section 2 for a more detailed functional description.
Actuators are installed and set at factory. The
following information is for reference and
troubleshooting.
D
IRECTION
OF
R
OTATION
:
Indicated on actuator housing and set at the factory.
The incoming damper is set to be normally closed
while the bypass damper shall be normally open.
See
and
M
ANUAL
P
OSITIONING
:
In case of component failure or service needs, the
actuators can by manually operated and locked in
place. Using a 3mm hex, rotate the actuator in the
direction indicated on the case. When at desired
location, lock in place using a screwdriver on the
locking pin located on the lower portion of the
housing (
C
ONTROL
S
IGNAL
:
A selection switch on the actuator housing
determines which type of proportional control is
being used. This should be set at the factory to 3 - 0-
10VDC Modulating.
Figure 5-1: Manual Positioning of Actuators
95°
ROTATING
LOCKING IN PLACE
Summary of Contents for 3000 EES
Page 10: ...NOTES 10 ...
Page 16: ...16 BLANK PAGE ...
Page 20: ...EES USER MANUAL SECTION 3 20 Figure 3 1 Identification EES 02250175 281 R00 ...
Page 21: ...SECTION 3 EES USER MANUAL 21 Figure 3 2 Wiring Diagram EES 02250175 264 R01 ...
Page 22: ...22 BLANK PAGE ...
Page 28: ...28 BLANK PAGE ...
Page 36: ...36 BLANK PAGE ...
Page 38: ...38 BLANK PAGE ...
Page 44: ...44 BLANK PAGE ...
Page 45: ...Section 8 45 EES USER MANUAL PARTS LISTS ...
Page 46: ...EES USER MANUAL SECTION 8 46 8 1 EES ENCLOSURE ASSEMBLY 02250175 279 R00 ...
Page 48: ...EES USER MANUAL SECTION 8 48 8 2 EES ELECTRICAL CONTROL ASSEMBLY 02250171 648 R00 ...
Page 50: ...EES USER MANUAL SECTION 8 50 8 3 EES DISCHARGE ENCLOSURE ASSEMBLY 02250171 646 R00 ...
Page 52: ...EES USER MANUAL SECTION 8 52 8 4 EES PACKAGE CLEAN AIR INLET OPTION 02250176 044 R00 ...
Page 54: ...54 BLANK PAGE ...
Page 55: ...NOTES 55 ...