![Sullair 3000 EES User Manual Download Page 35](http://html.mh-extra.com/html/sullair/3000-ees/3000-ees_user-manual_1390407035.webp)
SECTION 5
EES USER MANUAL
35
5.2
START-UP TEST
PROCEDURE
After installation and adjustments are complete, the
following test procedure can be performed to ensure
proper operation of the EES.
Settings
Required Results
Mixed Air Temp Controller – Lowest setting
Room Thermostat –Setting above display temperature
Outside Air Temp Controller – Highest setting
Compressor operating
1. 1 LED lit on mixed air temp controller
2. Incoming and bypass dampers operated to
min position
3. Rejected damper closed
4. Recovered damper open
Mixed Air Temp Controller - Lowest setting
Room Thermostat -Setting below display temperature
Outside Air Temp Controller - Highest setting
Compressor operating
1. 1 LED lit on mixed air temp controller
2. Incoming and bypass dampers operated to
min position
3. Rejected damper open
4. Recovered damper closed
Mixed Air Temp Controller - Lowest setting
Room Thermostat -Setting above display temperature
Outside Air Temp Controller - Lowest setting
Compressor operating
1. 1 LED lit on mixed air temp controller
2. Incoming damper fully open; bypass
damper fully closed
3. Rejected damper open
4. Recovered damper closed
Mixed Air Temp Controller - Lowest setting
Room Thermostat -Setting below display temperature
Outside Air Temp Controller - Lowest setting
Compressor operating
1. 1 LED lit on mixed air temp controller
2. Incoming damper fully open; bypass
damper fully closed
3. Rejected damper open
4. Recovered damper closed
Mixed Air Temp Controller - Highest setting
Room Thermostat -Setting above display temperature
Outside Air Temp Controller - Highest setting
Compressor operating
1. All LED lit on mixed air temp controller
2. Incoming damper fully open; bypass
damper fully closed
3. Rejected damper closed
4. Recovered damper open
Compressor on standby or without power
1. Incoming damper fully closed
2. Bypass damper fully open
3. Rejected damper fully closed
4. Recovered damper fully closed
Summary of Contents for 3000 EES
Page 10: ...NOTES 10 ...
Page 16: ...16 BLANK PAGE ...
Page 20: ...EES USER MANUAL SECTION 3 20 Figure 3 1 Identification EES 02250175 281 R00 ...
Page 21: ...SECTION 3 EES USER MANUAL 21 Figure 3 2 Wiring Diagram EES 02250175 264 R01 ...
Page 22: ...22 BLANK PAGE ...
Page 28: ...28 BLANK PAGE ...
Page 36: ...36 BLANK PAGE ...
Page 38: ...38 BLANK PAGE ...
Page 44: ...44 BLANK PAGE ...
Page 45: ...Section 8 45 EES USER MANUAL PARTS LISTS ...
Page 46: ...EES USER MANUAL SECTION 8 46 8 1 EES ENCLOSURE ASSEMBLY 02250175 279 R00 ...
Page 48: ...EES USER MANUAL SECTION 8 48 8 2 EES ELECTRICAL CONTROL ASSEMBLY 02250171 648 R00 ...
Page 50: ...EES USER MANUAL SECTION 8 50 8 3 EES DISCHARGE ENCLOSURE ASSEMBLY 02250171 646 R00 ...
Page 52: ...EES USER MANUAL SECTION 8 52 8 4 EES PACKAGE CLEAN AIR INLET OPTION 02250176 044 R00 ...
Page 54: ...54 BLANK PAGE ...
Page 55: ...NOTES 55 ...