April 13, 2009
115-V 20-Amp 60-Hz Self-Timed Unit
9
EXCHANGE PROCEDURE
115-V 20-Amp 60-Hz Self-Timed Unit
SUITMATE
®
EXCHANGE PROGRAM
The EXCHANGE PROCEDURE is to be used to effect the exchange of SUITMATE
®
units under the
“SUITMATE
®
Exchange Program.”
Note:
Retain ALL of the packaging material that the Exchange unit was delivered in.
REMOVAL OF DEFECTIVE SUITMATE
®
UNIT
1) Shut off power to the SUITMATE
®
unit’s circuit at the power panel – place a lockout tag on the circuit
breaker panel indicating that the breaker is not to be turned on except by authorized personnel and
disconnect the unit before doing any work on the SUITMATE
®
unit. Simply turning off a switch is
NOT enough.
2) Remove the cover of the weatherproof Junction Box, which contains the GFCI; remove the GFCI mounting
screws; disconnect the power feed wires from the GFCI terminals marked “LINE” and “NEUTRAL” and
disconnect the ground wire. Refasten the GFCI to the unit. The Exchange unit contains a GFCI.
3) Disconnect the power feed liquid tight raceway from the Junction Box.
4) Loosen the drain tube hose clamp or the P-trap compression fittings and slide the drain tube or P-trap off
the unit’s tailpiece.
5) Remove the lower fasteners anchoring the unit to the wall.
6) Lift the unit up to remove it from the Mounting Bracket.
INSTALLATION OF THE EXCHANGE SUITMATE
®
UNIT
1) When taking the Exchange unit out of the carton, be careful not to damage the carton as it will be needed
to return the defective unit.
2) Hang the Exchange unit on the Wall Mount Bracket by lowering the upper lip of the SUITMATE
®
unit case
over the top edge of the bracket. Be certain that the Exchange unit is centered on the Wall Mount Bracket.
Ease the SUITMATE
®
unit all the way down on the bracket and press down on both sides of the
plastic top at the back of the unit so it is firmly set in place. Check that the unit is level. If it is not level,
remove the unit, adjust the bracket, and re-hang the unit. A level installation is necessary to minimize
vibration and ensure proper drainage of wastewater.
3) Securing the lower mounting channel to the wall by reinstalling the fasteners removed in step 5 above
completes the mounting.
4) Reinstall the drain tube or P-Trap that was removed in step 4 above. Secure all wall connections.
5) Reconnect the power feed liquid tight raceway to the Junction Box, and the power leads and the ground
wire that were disconnected above. Be certain the hot lead is connected to the GFCI terminal marked
“HOT” and “LINE”, and the neutral lead is connected to the GFCI terminal marked “NEUTRAL” and “LINE”.
6) Secure the GFCI and your weatherproof Junction Box cover to the Junction Box.
WARNING!
For user safety it is imperative that the ground wire conductor be
reconnected and the GFCI is operating properly. If no ground conductor was
provided at the original installation, provide one now.
WWW.RESTROOMDIRECT.COM 704•937•2673 129 Oakpark Dr., Unit A, Mooresville, NC 28115
Summary of Contents for Swimsuit Water Extractor
Page 2: ...WWW RESTROOMDIRECT COM 704 937 2673 129 Oakpark Dr Unit A Mooresville NC 28115...
Page 70: ...WWW RESTROOMDIRECT COM 704 937 2673 129 Oakpark Dr Unit A Mooresville NC 28115...
Page 71: ...WWW RESTROOMDIRECT COM 704 937 2673 129 Oakpark Dr Unit A Mooresville NC 28115...
Page 72: ...WWW RESTROOMDIRECT COM 704 937 2673 129 Oakpark Dr Unit A Mooresville NC 28115...