FLAiR Series Installation, Operation & Maintenance Manual
Air Technology Systems, Inc.
4-6
Humidifier Inoperative
a. Water supply has been turned off
Connect and/or turn on water supply.
Note: See Humidifier
or not connected.
Manual for Additional
Help.
b. Humidifier Switch is in “Off” position.
Turn switch to “Auto/On” position.
c. Electrical connections are loose.
Tighten electrical connections.
d. Humidifier fuses or circuit breaker
Check for over current by the humidifier
tripped.
electrodes. Drain water from tank and
refill. Replace fuses or re-set circuit
breaker.
e. Relative humidity is above setpoint.
Adjust humidity setpoint.
f. Electrode canister change cylinder
1. Consult humidifier manual.
light is on.
2. Water conductivity is too low
and water is at the top of the
cylinder (see next item).
g. Water conductivity is too low.
Add a teaspoon of table salt to the water
through the top of the cylinder. Typically
only on initial start-up.
SYMPTOM
PROBABLE CAUSE
RECOMMENDATION