(©Aug, 2007)
FLAiR Series Installation, Operation & Maintenance Manual
Air Technology Systems, Inc.
4-4
SYMPTOM
PROBABLE CAUSE
RECOMMENDATION
Condenser Pressure
f. Water/glycol temperature too high.
Check flow and operation of drycooler.
g. Condenser pressure regulating valve
Adjust to obtain correct pressure.
setting too high.
h. Flow of water/glycol too low.
1. Check glycol solution level and
concentration.
2. Valves not open or partially open.
Repair/replace as needed
3. Air in system- bleed system.
4. Check all strainers and clean if needed.
i. Water/glycol solution not mixed prior
Remove solution and premix.
to adding to system.
Refill system.
Condenser Pressure too
a. Loss of refrigerant (indicated by
Locate and repair leak. Recharge system.
Low
bubbles in sight glass).
b. Condenser fan controls not set
Adjust or repair controls.
properly.
c. Water regulating valve adjusted
Readjust to 240-250 psig.
too low.
Noisy Compressor
a. Expansion valve stuck in open
Ensure feeder bulb is tight on suction line.
position (abnormally cold suction line).
Check operation and superheat.
b. Broken compressor valve
Replace compressor.
(compressor knocking, suction
pressure rises faster than 2lbs/min
after shutdown).
c. Worn or scarred compressor
Replace compressor.
bearings.
d. Liquid slugging.
System overcharged. Reclaim excess
refrigerant.
e. Scroll compressor not properly
Phase correctly at main power source.
phased.
DO NOT REWIRE COMPRESSOR.
Compressor Fails to Start
a. Temperature setpoint too high.
Adjust to desired temperature.
b. Compressor internal protector
Check compressor for short circuit
is open.
or ground.
c. Complete loss of refrigerant charge
Locate and repair leak. Recharge system.
(low pressure safety switch).
d. Condenser pressure too high
Check condenser for obstructions.
(high pressure safety switch).
too High (cont.)
Summary of Contents for FLAIR series
Page 1: ...FLAiR Series Installation Operation Maintenance Manual Aug 2007 Air Technology Systems Inc ...
Page 42: ... Aug 2007 FLAiR Series Installation Operation Maintenance Manual Air Technology Systems Inc ...
Page 44: ... Aug 2007 FLAiR Series Installation Operation Maintenance Manual Air Technology Systems Inc ...
Page 46: ... Aug 2007 FLAiR Series Installation Operation Maintenance Manual Air Technology Systems Inc ...
Page 48: ... Aug 2007 FLAiR Series Installation Operation Maintenance Manual Air Technology Systems Inc ...