(©Aug, 2007)
FLAiR Series Installation, Operation & Maintenance Manual
Air Technology Systems, Inc.
2-11
2.7.5
Glycol Cooled Systems (G Models)
Systems equipped with a glycol-cooled system/pump
package require field wiring between the glycol unit
and pump package, (see Figure 9). The installer must
wire two control conductors from the terminal board
within the glycol unit, to the pump package electrical
box. Refer to the electrical schematic supplied with
your unit for the number of field wires needed and
appropriate wire terminations required for your specific
system.
Figure 9- Interconnecting Field Wiring Glycol Systems
(TO BE INSTALLED IN ACCORDANCE
(GLYCOL UNITS ONLY)
GPS-005/010-( )
ELECTRIC
24VAC
PUMP PACKAGE
BOX
SEE NOTES 1 & 2
WITH NFPA 70, N.E.C.)
INTERCONNECTING FIELD WIRING
MAIN POWER SUPPLY
208-460V/1PH-3PH/60Hz
DRYCOOLER
L3
L1
L2
SEE NOTE 3
4 CONDUCTOR NON-
SHIELDED CABLE
SHIELDED CABLE
2 CONDUCTOR
6 CONDUCTOR PHONE TYPE
NON-SHIELDED CABLE
WITH NFPA 70, N.E.C.)
SEE NOTE 1
INTERCONNECTING FIELD WIRING
(TO BE INSTALLED IN ACCORDANCE
MAIN POWER SUPPLY
208-460V/1PH-3PH/60Hz
FCS-018/060-WG
2. NUMBER OF CONDUCTORS VARY DEPENDING ON NUMBER OF FAN MOTORS.
1. PHANTOM WIRES ( ) NOT APPLICABLE FOR SINGLE PHASE POWER SUPPLIES.
NOTES:
3. OPTIONAL REMOTE MOUNTED DEVICES.
REMOTE TEMPERATURE/
HUMIDITY SENSOR
SHIELDED CABLE
(NUMBER OF
CONDUCTORS VARY)
Summary of Contents for FLAIR series
Page 1: ...FLAiR Series Installation Operation Maintenance Manual Aug 2007 Air Technology Systems Inc ...
Page 42: ... Aug 2007 FLAiR Series Installation Operation Maintenance Manual Air Technology Systems Inc ...
Page 44: ... Aug 2007 FLAiR Series Installation Operation Maintenance Manual Air Technology Systems Inc ...
Page 46: ... Aug 2007 FLAiR Series Installation Operation Maintenance Manual Air Technology Systems Inc ...
Page 48: ... Aug 2007 FLAiR Series Installation Operation Maintenance Manual Air Technology Systems Inc ...