CyberOne EC DX IOM Manual
the remote condenser/condensing unit electrical box.
A separate equipment ground lug is provided within the
electrical box for termination of the earth ground wire. Refer
to the electrical drawing supplied with your unit and the wiring
diagram supplied with the condenser (typically located in the
condenser electric box).
2.7.4.1
Remote Condenser (AR Models)
Control wires are not required between the remote condenser
and the A/C system (see Figure 13). As an option, control
wiring may be installed for the system controller to enable
condenser operation only when the compressor is running.
You must remove the jumper from the remote
condenser terminal board (see the condenser wiring
diagram). Wire 24 VDC control conductors from the
terminal board within the A/C unit to the remote
condenser terminal board. If control wires aren’t
installed (and the jumper remains in place), the
condenser is always enabled and will turn on and off
based on the condenser’s pressure control settings.
Refer to the electrical drawing for the correct number of
field wires needed and for appropriate wire
terminations required specifically for your system.
19